Owner’s Manual for Generac PWRcell Inverter
3
General Information
Section 2: General Information
Specifications
Description
Units
X7602
X11402
Max. cont. grid-tied AC power @ 122º F (50º C)
kW
7.6
11.4
Max. cont. islanded AC power without an external
transfer switch
1
kW
7.6
7.6
Max. cont. islanded AC power w/ external transfer
switch and single 6 module battery cabinet
2
kW
9.0
9.0
Max. cont. islanded AC power w/ external transfer
switch and 2 battery cabinets (8 modules minimum)
2
kW
11.0
Range 9.6 to 11.0*
Peak motor starting current (2 sec)
A rms
50
Normal output frequency AC
Hz
60
Grid Voltage Line to Neutral (L-N)
VAC
120
Grid Voltage Line to Line (L-L)
VAC
240
208
Peak efficiency
%
97.3
97.7
Allowable split phase imbalance
%
Up to 30%
CEC weighted efficiency
%
96.5
97.5
AC terminals wire size
AWG
14 to 6
DC terminals wire size
AWG
18 to 6
STOP terminals wire size
AWG
30 to 14
Weight
lb (kg)
70.9 (32.1)
Thermal management
-
forced convection
Weatherization rating
-
NEMA Type 3R
Enclosure Material
-
powder-coated steel
Description
Units
Min
Nominal
Max
REbus voltage
V
360
380
420
REbus current
A
30
†
REbus Input short circuit current
3
A
30
REbus Input source backfeed current to input source
A
30
Output power factor rating AC
-
1
Operating voltage range AC, X7602 Series (L-N)
V rms
10
6
120
13
2
Operating voltage range AC, X7602 Series (L-L)
V rms
21
2
240
26
4
Operating voltage range AC, X11402 Series (L-N)
V rms
10
6
120
13
2
Operating output voltage range AC, X11402 Series (L-L)
V rms
184
208
228
Continuous output current AC islanded
1
A rms
32
PCS controlled current grid-tied
A rms
32
Continuous output current AC grid-tied
A rms
42
Output fault current duration
A / ms
50 / 2000
Full Power operating ambient temperature range
4
°F (°C)
-4 (-20)
+122 (+50)
Utility interconnection voltage and frequency
trip limits and trip times
See Voltage and Frequency Trip Thresholds in the PWRcell
Inverter Installation Manual for more information.
Trip voltage and frequency limits
Trip voltage accuracy
Trip time accuracy
-
2% +/-2 cycles
1
When islanded, continuous power output is restricted to 7.68kW unless backup power is routed through an external transfer
switch.
2
Peak performance, values provided for 104º F (40º C)
3
Rating for one DC input. Four total.
4
Includes ambient temperature rising from inverter operation.
* In Island mode XVT11402 Protected loads only supply 2 phases 120 VAC L-N, 208 L-L which results in lower power than in
grid tied 3 phase mode. The low value of the range is for full L-L loading while high value of the range is full L-N loading.
†
Inverter limits its REbus current to adhere to its AC power rating.
Total REbus current capability from multiple REbus
sources may safely exceed this value as the inverter safely limits the amount utilized.
Содержание PWRcell APKE00014
Страница 4: ...iv Owner s Manual for Generac PWRcell Inverter This page intentionally left blank ...
Страница 18: ...Operation 14 Owner s Manual for Generac PWRCell Inverter This page intentionally left blank ...
Страница 20: ...16 Owner s Manual for Generac PWRCell Inverter Maintenance This page intentionally left blank ...
Страница 21: ...Owner s Manual for Generac PWRcell Inverter 17 Maintenance This page intentionally left blank ...
Страница 22: ...18 Owner s Manual for Generac PWRCell Inverter Maintenance This page intentionally left blank ...
Страница 23: ...This page intentionally left blank ...