Operation
16
Owner’s Manual for 7.5 kW PowerPact™
Auxiliary Shutdown Switch
All generators are provided with an external means to
shut down the generator that complies with the 2017
NEC code requirement. The primary generator shutdown
sequence is described in the previous topic.
See
. An auxiliary shutdown switch is located
on the exterior of the generator back panel. This switch
shuts down the generator and disables restarts.
Figure 3-5. Auxiliary Shutdown Switch
NOTE:
Whenever possible, perform the primary
shutdown procedure before disabling the generator with
the auxiliary shutdown switch.
NOTE:
If the auxiliary shutdown switch is open (O), the
generator will not start. The controller displays a High
Temperature alarm and the High Temperature LED on
the controller flashes until the switch is closed (I). Once
the switch is closed (I), the generator will return to either
AUTO mode or OFF mode.
NOTE:
The controller displays the same alarm message
for either a High Temperature Alarm or an open auxiliary
shutdown switch.
005570
005570
Содержание PowerPact G0069981
Страница 14: ...General Information 10 Owner s Manual for 7 5 kW PowerPact This page intentionally left blank ...
Страница 30: ...Troubleshooting 26 Owner s Manual for 7 5 kW PowerPact This page intentionally left blank ...
Страница 33: ...Quick Reference Guide Owner s Manual for 7 5 kW PowerPact 29 This page intentionally left blank ...
Страница 34: ...Quick Reference Guide 30 Owner s Manual for 7 5 kW PowerPact This page intentionally left blank ...
Страница 35: ......