Generac Power Systems PCRGM1 Скачать руководство пользователя страница 2

Install Verification

1.

Navigate  to  the  Beacon  device  page  on  the

PWRcell  Inverter  control  screen  and  press  the

center button.

2.

Select the ‘Installer Tool’ item from the menu and

click ‘Confirm’. This will activate the Beacon’s Wi-Fi

network.

3.

Use a smart phone or laptop to connect to the Wi-

Fi  network  ‘REbus_Beacon_xxxx’,  where  xxxx  is

the last 4 digits of the RCP number found on the

front of the Beacon.

4.

Enter the password (labeled “CODE”) found on the

back side of the Beacon.

5.

Open  a  web  browser  and  enter  '10.10.10.10',  in

address bar, to access the installer tool page.

6.

Select 'RGM/LTE Kits' on the left panel. Check the

RGM Kit Status to verify the kit has been installed

correctly. RGM Kit Status should read “

Installed”

when unit is installed correctly. “

Not Found”

 is dis

-

played when unit is incorrectly installed. See image

below.

RGM / LTE Kit Status

Inverter

00010007

Revenue - Grade Meter (RGM)

Beacon

00010012

RGM Kit Status:

Installed

Battery

00010008

Serial Number:

SAH4046AAXXXX

PV

00010003

Total Power:

2639 W

PV

00010003

L1 Voltage:

120.1 V

PV

00010003

L1 Current:

10 A

PV

00010003

L2 Voltage:

119.8 V

PV

00010003

L2 Current:

12 A

Owner Information

LTE Cellular Modem

Compliance PDF

Proof of Compliance

LTE Kit Status:

Not Found

RGM / LTE Kits

®

Disp.

Fuse

Fuse

CT

AT

S

 

Beacon 

St

op

Tech.  Se

rv

ic

e

Modem

DC Breakers

L1 N L2 

Fuse Fuse

Insert the stripped end of the 
included AC voltage cable into the 3
position screw terminal labled  
“GEN Inhibit” and tighten screws. 
Then plug the 4-pin connector end to  

L1 : Black
N : White
L2 : Red

Insert the two included CTs into CT ports 

1 and 2 on the PWRView meter, then clamp 

the CTs around AC wires attached to the 

right side screw terminals.  
CT1 : L1 & L1 Protected

CT2 : L2 & L2 Protected

Note:

 'SOURCE THIS SIDE' marking on the 

CTs should face towards screw terminals.
Ensure both wires enter the CT from the 

same direction. 

Important: Use the included cable ties to 

bundle up a short section of AC wires. This 

prevents the CTs from opening due to wires 

pulling away from each other.

Locate the free hanging 6-pin

connector cable from underneath
the DC breakers. Insert connector
into the COMMS port on PWRView 

meter. 

N2

L1

L2

N1

L1

L2

L3

(Protcd)

(Protcd)

(Protcd)

Wiring Diagram

the AC port on PWRView meter.

011164

Part No. A0000880178    Rev A   0

8

/

03

/2020

©2020 Generac Power Systems, Inc.

All rights reserved.

Specifications are subject to change without notice.

No reproduction allowed in any form without prior written consent from 

Generac Power Systems, Inc.

Generac Power Systems, Inc.

S45 W29290 Hwy. 59

Waukesha, WI 53189

1-888-GENERAC (1-888-436-3722)

www.generac.com

Отзывы: