Troubleshooting
44
Owner’s Manual for MLT6SMD Light Tower
If problems continue, contact Generac Mobile Products, LLC at 1-800-926-9768 for assistance.
Problem
Possible Cause
Solution
Unit cranks, but will not start
Low fuel level.
Verify fuel level in tank.
Fuel flow obstructed.
Check fuel pump operation.
Inspect fuel supply hose from tank to fuel filter for
cracks and abrasion.
Inspect for gelled fuel in fuel system in cold
weather, especially at fuel filter.
Air in fuel system.
Purge air from fuel system.
Restricted air filter.
Inspect air filter for blockage.
Glow plug(s) inoperable.
Refer to OEM engine operator’s manual for
additional information.
Unit starts, but stumbles and dies
Low ambient temperature.
Verify if ambient temperature is within unit limits.
Intake heater inoperable.
Inspect engine air inlet heater functionality.
Air in fuel lines.
Purge air from fuel lines.
High coolant temperature shutdown
Low coolant level.
Allow engine to cool, then check coolant level in
radiator. Add coolant if needed.
Blockage in radiator.
Inspect radiator surroundings for blockage and
remove any foreign matter.
Debris on radiator face.
Broken coolant pump belt.
Inspect for visible leaks. Check tension of water
pump drive belt.
Cooling fan inoperable.
Remove load on generator and restart engine.
Check coolant temperature and shut engine down
immediately if it starts to overheat.
Low oil pressure shutdown
Low oil level.
Check oil level. Add oil if necessary.
Oil pump inoperable.
Contact a GMP ASD.
Unit stalls when export power is used
Load exceeds unit rating.
Turn outlet breaker ON and load sense switch
OFF, confirm generator output is 60 Hz ± 2 Hz.
Reapply load.
One or more lights do not turn on
Light breaker tripped.
Inspect light breakers.
Lights not turned on.
Inspect electronic control to see if lights are on.
Turn lights on.
The lights are flashing
Dusk-to-dawn sensor
adjustment needed.
Adjust the dusk-to-dawn sensor according to
.
Low generator frequency.
Verify AC frequency is >40hz.
Содержание MLT6SMD
Страница 16: ...Introduction and Safety 12 Owner s Manual for MLT6SMD Light Tower This page intentionally left blank ...
Страница 32: ...General Information 28 Owner s Manual for MLT6SMD Light Tower This page intentionally left blank ...
Страница 42: ...Operation 38 Owner s Manual for MLT6SMD Light Tower This page intentionally left blank ...
Страница 49: ...Wiring Diagrams Owner s Manual for MLT6SMD Light Tower 45 Section 6 Wiring Diagrams AC Wiring 75022 ...
Страница 54: ...Wiring Diagrams 50 Owner s Manual for MLT6SMD Light Tower This page intentionally left blank ...
Страница 59: ......