General Information
Owner’s Manual for MLT3060M-K Light Tower
21
Scheduler Screen
See
. The Scheduler screen enables the
operator to program specific times for the lights to turn
ON and OFF. Once programmed, the Scheduler will start
the engine and illuminate the lights until the designated
shutdown time.
Figure 2-10. Scheduler Screen
NOTE:
This feature will only work in AUTO mode.
Maintenance Screens
See
. The information displayed on the
maintenance screens can be used to identify, diagnose
and troubleshoot unit shutdown conditions and poor unit
performance.
Figure 2-11. Maintenance Screens
To enter the navigation menu, use the following
procedure:
1. Press both the
↑
and
↓
buttons simultaneously.
2.
To select the required icon, press the
↑
button to
cycle right and the
↓
button to cycle left until the
desired operator screen section is reached.
3.
Once the desired icon is at the top, press the
Select (
) button to enter that operator screen
section.
NOTE:
Every time the operator screens are entered, the
home icon will be located at the top of the screen.
Alarms Screen
See
. The Alarms (
) screen displays all the
alarms, warnings, and engine Diagnostic Trouble Code
(DTC) faults. When an alarm occurs, the controller
automatically switches to this screen and remains there
until the alarm is cleared. The Stop LED also flashes.
Figure 2-12. Alarms Screen
•
Warnings
are non-critical alarm conditions and do
not affect the operation of the unit. They serve to
draw attention to an undesirable condition. By
default, warning alarms are self-resetting when the
fault condition is removed.
•
Electrical trips
stop the generator in a controlled
manner. On initiation of the electrical trip condition,
the controller de-energizes all the outputs,
including the lights, to remove the load from the
generator. Once this has occurred, the controller
starts the cooling timer and allows the engine to
cool off-load before shutting down the engine.
•
Shutdown alarms
stop the generator immediately.
On initiation of the shutdown condition, the
controller de-energizes all the outputs, including
the lights, to remove the load from the generator.
Once this has occurred, the controller shuts the
unit down immediately to prevent further damage.
•
DTC faults
are displayed by the controller.
Icon
Description
Home screen
Alarms screen
Maintenance screen
Event log screen
About screen
002329
003779
003780
Содержание Magnum MLT3060K
Страница 28: ...General Information 24 Owner s Manual for MLT3060M K Light Tower This page intentionally left blank...
Страница 51: ...Wiring Diagrams Owner s Manual for MLT3060M K Light Tower 47 This page intentionally left blank...
Страница 52: ...Wiring Diagrams 48 Owner s Manual for MLT3060M K Light Tower This page intentionally left blank...
Страница 54: ...50 Owner s Manual for MLT3060M K Light Tower This page intentionally left blank...
Страница 55: ......