Operation
36833 C
MGG100M Operating Manual
37
GENERATOR OUTPUT CONNECTIONS
CAUTION
Equipment damage. Exceeding rated voltage and current will damage the auxiliary contacts.
Verify that voltage and current are within specification before energizing this equipment.
(000134a)
Temperature and Altitude Derating
Derating is the reduction of available power for operating tools and accessories connected to the receptacles. All
units are subject to derating due to altitude and temperature. Typical reductions in performance are 2–4% for every
1000 ft (305 m) of elevation and 1% per 10ºF (3–5ºC) increase in ambient air temperature over 72ºF (22ºC).
Customer Convenience Receptacles
The customer convenience receptacle is attached to the outside of the customer disconnect switch box (
).
The receptacle is a 120VAC duplex outlet rated at 20A with Ground Fault Circuit Interrupt (GFCI) protection.
The receptacle is not routed through the MLCB, but through an independent circuit breaker, located directly next to
it. The breaker is sized to the maximum rating of the receptacle.
Power to the receptacles is available when the generator is running, even if the main circuit
breaker is OFF (O).
MAKE SURE THAT ANY EQUIPMENT CONNECTED TO THE
CONVENIENCE RECEPTACLES IS TURNED OFF BEFORE TURNING THE BREAKERS
ON
and the output voltage is correct for equipment connected to the receptacles. Improper
voltage may cause equipment damage or malfunction.
Figure 20 - Customer Convenience Receptacle
02198
Содержание Magnum MGG100M
Страница 4: ...This Page Intentionally Left Blank 36833 C MGG100M Operating Manual iv...
Страница 8: ...This Page Intentionally Left Blank 36833 C MGG100 Operating Manual viii...
Страница 14: ...Safety 6 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Страница 52: ...Operation 44 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Страница 76: ...Wiring Diagrams 68 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Страница 83: ......