MISCELLANEOUS MAINTENANCE

CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt
and moisture that accumulates on internal generator
windings have an adverse effect on insulation resist-
ance.

Periodically clean generator exterior surfaces. A soft
brush may be used to loosen caked on dirt. Use a vacu-
um system or dry, low pressure air to remove any accu-
mulations of dirt. The generator is housed inside an
all-weather enclosure, clean the enclosure with a soft,
damp cloth or sponge and water.

Once each year have the generator cleaned and inspect-
ed by an Authorized Service Dealer. That dealer will use
dry, low pressure air to clean internal windings. Parts
inside the control console should be cleaned and
inspected at this time as well.

Finally, have the insulation resistance of stator and
rotor windings checked. If insulation resistances are
excessively low, the generator may require drying.

BATTERY

All lead-acid storage batteries discharge when not in
use. Refer to specific instructions and warnings that
accompany the battery. If such information is not avail-
able, observe the following precautions when 
handling a battery:

• DO NOT use jumper cables and a booster battery to

crank or start the generator engine.

• DO NOT recharge a weak battery while it is installed

in the generator. Remove battery from generator and
recharge in a well-ventilated area, away from fuel
vapors, sparks, heat or flames.

• Battery electrolyte fluid is an extremely caustic 

sulfuric solution that can cause severe burns. DO
NOT permit fluid to contact eyes, skin, clothing,
painted surfaces, wiring insulation, etc. If any battery
fluid is spilled, flush the affected area with clear
water immediately.

• Always wear safety glasses, rubber apron and gloves

when handling a battery.

• Batteries give off explosive hydrogen gas while 

charging. The gas can form an explosive mixture
around the battery for several hours after charging.
Any spark, heat or flames can ignite the gas and
cause an explosion which can shatter the battery,
causing blindness or other serious injury.

BATTERY MAINTENANCE

The battery should be inspected per the “Service
Schedule,” Section 6. The following procedure should
be followed for inspection:

1. Inspect the battery posts and cables for tightness

and corrosion. Tighten and clean as necessary.

2. Check the battery fluid level of unsealed batteries

and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTERIES.

3. Have the state of charge and condition checked.

This should be done with an automotive-type bat-
tery hydrometer.

Storage batteries give off explosive hydrogen gas.
This gas can form an explosive mixture around
the battery for several hours after charging. The
slightest spark can ignite the gas and cause an
explosion. Such an explosion can shatter the bat-
tery and cause blindness or other injury. Any area
that houses a storage battery must be properly
ventilated. Do not allow smoking, open flame,
sparks or any spark producing tools or equipment
near the battery.

Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe burns.
Do not permit fluid to contact eyes, skin, clothing,
painted surfaces, etc. Wear protective goggles,
protective clothing and gloves when handling a
battery. If fluid is spilled, flush the affected area
immediately with clear water.

Do not use any jumper cables or booster battery
to crank and start the generator engine. If the
battery has completely discharged, remove it from
the generator for recharging. 

Be sure the Auto/Off/Manual switch is set to the
OFF position before connecting the battery cables.
If the switch is set to AUTO or MANUAL, the gen-
erator can crank and start as soon as the battery
cables are connected.

Be sure the utility power supply is turned off, or
sparking may occur at the battery posts as the
cables are attached and cause an explosion.

BATTERY REPLACEMENT

When replacing batteries, use the same number and the
type of battery that follows:

Note:

The BCI number should be located directly 
on the battery.

‹

!

!

!

DANGER

‹

‹

‹

Section 4 — Maintenance

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

BCI Group No.

CCA

26/26R

525 @ 0 deg. F

Содержание Guardian 004188-1

Страница 1: ...d Prepackaged Standby Generators Model Numbers Natural Gas 004188 1 004370 2 004474 1 Liquid Propane Vapor 004189 1 004371 2 004475 1 ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLA...

Страница 2: ...l explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equipment We strongl...

Страница 3: ...Method 9 Total Circuit Isolation Method 9 Grounding the Generator 9 Generator AC Neutral Connections 10 Transfer Switch Start Signal Connections 10 Battery Installation 10 Preparation Before Start Up...

Страница 4: ...ator is installed operated and serviced in accordance with the manufacturer s instructions and recommen dations Following installation do nothing that might render the unit unsafe or in noncompliance...

Страница 5: ...operating Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers...

Страница 6: ...sfer switch on a firm sturdy support ing structure To prevent switch distortion level the switch if neces sary This can be done by placing washers between the switch enclosure and the mounting surface...

Страница 7: ...OOLANT TEMPERATURE SWITCH Normally open N O thermostatic switch has sensing tip which is immersed in captive coolant Should coolant temperature exceed about 230 F 110 C the switch contacts close which...

Страница 8: ...if the fuse is blown Replace the fuse with one of the same size type and rating Generac normally uses an AGC fuse rated at 30 amps UNPACKING UNPACKING PRECAUTIONS Handle shipping cartons and crates w...

Страница 9: ...crank or start the engine before it has been properly serviced with the recommend ed oil may result in an engine failure COOLANT RECOMMENDATIONS Use a mixture of half low silicate ethylene glycol bas...

Страница 10: ...ING HANDBOOK obtainable from the Food and Energy Council 909 University Avenue Columbia MO 65201 ASAE EP 364 2 INSTALLATION AND MAINTE NANCE OF FARM STANDBY ELECTRIC POWER available from the American...

Страница 11: ...age amperage capacity of the generator set When this method is used it is difficult to overload the gener ator The transfer switch must meet the following requirements It must have an ampere rating eq...

Страница 12: ...y with clear water Do not dispose of the battery in a fire The bat tery is capable of exploding Do not open or mutilate the battery Released electrolyte can be toxic and harmful to the skin and eyes T...

Страница 13: ...30 hours of operation Engine Coolant Have the engine cooling system properly filled with the recommended coolant mixture Check the system for leaks and other problems See Specifications and Coolant B...

Страница 14: ...ng with the periodic maintenance schedule for the genera tor set AUTO OFF MANUAL SWITCH Use this 3 position switch as follows Set the switch to Auto for fully automatic operation See Automatic Operati...

Страница 15: ...such as a utility main line circuit breaker The utility power source now powers the loads AUTOMATIC OPERATION To set the system for fully automatic operation proceed as follows Check that load circui...

Страница 16: ...rque Specs 2 Retorque intake and exhaust manifold See Torque Specs 3 Check engine compression 4 Check valve clearance COOLING SYSTEM Air intake and outlet openings in the generator com partment must b...

Страница 17: ...INSPECT COOLING SYSTEM Inspect engine cooling system at least once each month Check hoses for damage deterioration leaks etc Correct any discrepancies found Check hose clamps for tightness CHECK ENGI...

Страница 18: ...il leaks CHANGING THE ENGINE AIR CLEANER To replace the engine air cleaner part number 59402 simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before...

Страница 19: ...as and cause an explosion which can shatter the battery causing blindness or other serious injury BATTERY MAINTENANCE The battery should be inspected per the Service Schedule Section 6 The following p...

Страница 20: ...l and add oil as needed 2 Engine is overheated 2 Check cooling system for leaks 3 Defective Low Oil Pressure Switch 3 Replace switch 4 Defective Coolant Temperature Switch 4 Replace switch 5 Defective...

Страница 21: ...FORE removing the battery cable to prevent an over current condi tion from burning out sensitive control panel components and circuits Following all maintenance reverse these steps to insure the unit...

Страница 22: ...ant thermal protection level Correct as necessary 5 Check the natural gas delivery system on gas engine driven units Tighten connections as necessary 6 Check the air inlets and outlets for debris Clea...

Страница 23: ...connections or components and abnormal operating conditions Correct as necessary 14 Start and exercise the unit at full rated load use a load bank if the site load is not enough for at least 2 hours l...

Страница 24: ...22 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Wiring Diagram Control Panel 1 Phase Drawing No 0A2803 D...

Страница 25: ...Generac Power Systems Inc 23 Section 7 Electrical Data Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Wiring Diagram Control Panel 1 Phase Drawing No 0A2803 D...

Страница 26: ...24 Generac Power Systems Inc Section 7 Electrical Data Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Electrical Schematic Control Panel 1 Phase Drawing No 0A2802 B...

Страница 27: ...Section 7 Electrical Data Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Wiring Diagram 1 5L Gas Engine Drawing No 0A7176 A Generac Power Systems Inc 25 AC OUTLET...

Страница 28: ...OS LOW OIL SWITCH ISC IGNITION SYSTEM CONTACT GRD GROUND EH ENGINE HEATER DCA DC ALTERNATOR CC CONTROL CONTACTOR 12V BATTERY FED CIRCUIT TO 120V 15A UTILITY 0 BLACK GREEN WHITE EH 0 CC 16 RED SM TO CO...

Страница 29: ...15 10 SWAGE FASTENER W NYLON WASHER ITEM PART NO QTY DESCRIPTION 10 32990 6 BUMPER 11 C2164 1 LATCH 13 29107 6 GROMMET 3 16 7 8 14 A1694 5 BUTTON PLUG 1 1 2 15 91297 063 3 GROUND WIRE ASSEMBLY 16 9129...

Страница 30: ...0 24 26 31 8 23 42 50 27 8 27 36 1 2 31 21 3 2 17 26 19 18 26 55 2 23 16 28 3 1 14 53 10 27 12 27 27 43 2 2 11 54 1 13 56 15 28 23 2 1 29 1 20 23 25 28 5 4 47 52 51 6 28 9 23 4 7 27 4 3 5 27 4 Section...

Страница 31: ...NC 27 089961 24 FT FOAM STRIP 3 4 X 1 4 28 022473 20 WASHER FLAT 1 4 ZINC 29 082570 1 PLUG PLASTIC 4 PLUG BTTN 425 30 039253 12 SCREW HHC M8 1 25 X 20 G8 8 31 042568 14 SCREW HHC M6 1 0 X 20 G8 8 32 0...

Страница 32: ...30 Generac Power Systems Inc Section 8 Exploded Views and Parts Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Exploded View Control Panel 15 and 20 kW Drawing No 0A2872 F...

Страница 33: ...x 12MM 35 056739 1 SOLENOID RELAY 12VDC ITEM PART NO QTY DESCRIPTION 36 0C2512 1 GROMMET 1 16 1 3 8 37 0C2513 2 GROMMET 1 8 1 3 4 38 061395 TRANSFORMER CURRENT 100 5 058318 TRANSFORMER CURRENT 150 5...

Страница 34: ...15 VDC PANEL FACE ENLARGED VIEW V 44 53 A Hz CB 40 46 34 VIEW ON C B 63 19 18 51 17 61 50 24 16 64 CMA 55 C 42 65 64 31 37 37 32 36 6 58 30 23 45 64 28 52 39 38 3 41 14 VIEW ON A 28 56 40 4 49 5 62 21...

Страница 35: ...ENOID 12VDC PNL MNT 36 072252 2 GROMMET 1 37 X 06 X 1 00 ITEM PART NO QTY DESCRIPTION 37 063212 1 GROMMET 1 75 X 12 X 1 50 38 058318 2 TRANSFRM 150A TO 5A 5VA 39 033121 2 SCREW HHC 10 32 X 1 2 40 0492...

Страница 36: ...ne block To engine bypass 14 30 12 33 34 water inlet 8 tube On block 8 24 12 29 19 8 8 21 A 20 9 24 3 To thermostat adapter 14 12 17 4 17 7 16 7 7 5 34 33 14 13 6 11 11 12 Section 8 Exploded Views and...

Страница 37: ...SCREW CRMPTIT 1 4 20 X 5 8 18 056892 4 SCREW CRIMPTITE 10 24 X 3 8 19 0A6284 1 HOSE LOWER RADIATR 20 0A6258 1 HOSE UPPER RADIATR 21 029032 1 HOSE 9 32 ID 22 031669 4 BOLT CARR 1 4 20 X 1 3 4 JS500 23...

Страница 38: ...On block 3 8 20 8 8 21 9 A 8 18 33 3 12 34 4 17 To engine bypass 7 on intake manifold Midway up engine block 37 30 7 16 13 34 33 17 15 5 7 11 14 12 6 A 29 31 24 12 12 11 12 Section 8 Exploded Views a...

Страница 39: ...10 24 X 3 8 19 0A6284 1 HOSE LOWER RADIATOR 20 0A6258 1 HOSE UPPER RADIATOR 21 029032 1 HOSE 9 32 ID 24 022127 1 NUT HEX 1 4 20 STEEL 25 022145 8 WASHER FLAT 5 16 ZINC 26 022129 8 WASHER LOCK M8 5 16...

Страница 40: ...8 45771 12 NUT HEX M8 1 25 9 71956 4 WASHER VIBRATION ISOLATOR 10 51730 2 CAPSCREW HEX HEAD M8 1 25 x 60MM 12 57821 2 CAPSCREW HEX HEAD M8 1 25 x 40MM 13 21991 1 STRAP GROUNDING 14 27482 1 WASHER STA...

Страница 41: ...MOUNTING 3 070936 2 DAMPENER VIBRATION 4 070936C 2 DAMPENER VIBRATION 5 039253 8 SCREW HHC M8 1 25 X 20 G8 8 6 022145 12 WASHER FLAT 5 16 ZINC 7 022129 12 WASHER LOCK M8 5 16 8 045771 12 NUT HEX M8 1...

Страница 42: ...16 18 STEEL 9 022129 6 WASHER LOCK M8 5 16 10 036449 1 SADDLE 2 INCH 11 076032 1 CHANNEL MUFFLER SUPPORT 12 039253 4 SCREW HHC M8 1 25 X 20 G8 8 13 045771 4 NUT HEX M8 1 25 G8 YEL CHR 14 0C3683 1 GUA...

Страница 43: ...HAUST 6 0C1068 1 SUPPORT MUFFLER 1 5L 7 0C1412 1 ELBOW EXHAUST 45 DEG 8 0A5728 1 MUFFLER 1 6 1 5L SAE 9 060366 2 STRAP MUFFLER 6 DIA 10 066889 4 SCREW HHC M8 X 1 25 X 20MM 11 022145 4 WASHER FLAT 5 16...

Страница 44: ...70 X 2 240V 39782 BRKT 039766 1 CIRCUIT BREAKER 90 X 2 240V 39782 BRKT 0A2077 1 CIRCUIT BREAKER 125 X 2 120 240V 39783 BRKT 5 023965 2 SCREW RHM 8 32 X 3 8 6 022264 2 WASHER LOCK 8 M4 5 2 6 3 4 1 42...

Страница 45: ...SHER LOCK M4 10 051787 2 SCREW HHC M4 0 7 X 16 G8 8 11 079847 1 BOX CMA ITEM PART NO QTY DESCRIPTION 12 0A8504 1 DECAL CMA LABEL 0A8504A 1 DECAL CMA LABEL 13 022661V 083 TUBING SHRINK 19 ID RED 14 038...

Страница 46: ...4 X 20 00 3 038805B 1 CABLE BATT BLK 4 X 23 00 4 0742600131 1 ASSY WIRE 16 RED 1 6 5 022131 1 WASHER FLAT 3 8 ZINC 6 046526 1 WASHER LOCK M10 7 052213 1 SCREW HHC M10 1 25 X 20 G8 8 8 059567 2 BOLT B...

Страница 47: ...M 2 X 5 8 SELF TAP 6 043146 3 SCREW HHC M6 1 0 X 10 G8 8 7 022097 5 WASHER LOCK M6 1 4 8 064526 2 SCREW TAP HWH 6 25 X 3 8 ZINC 9 098783 1 LEVER STEPPER MOTOR 10 037398 2 NUT LOCK HEX 10 32 NYL INS 11...

Страница 48: ...15 14 17 To Blower Housing 32 23 24 35 1 21 28 7 22 33 10 29 16 30 18 2 6 19 20 31 21 4 To Engine Crankshaft 26 Section 8 Exploded Views and Parts Guardian Liquid cooled 15 kW 20 kW and 25 kW Generato...

Страница 49: ...75476 4 SCREW PPHM M4 0 7 X 16 12 0A5601 1 COVER REAR BEARING CARRIER 13 075554B 4 BOLT STATOR X 16 LG 14 0A9375 4 SCREW RHM 10 24 X 2 15 022152 4 WASHER LOCK 10 16 097146 1 FAN RING GEAR ASSEM 17 042...

Страница 50: ...0 19 34 28 32 20 31 29 30 TO ENGINE AT X BLOCK MOUNT 14 1 14 11 9 15 33 D 4 4 27 15 6 9 11 35 8 36 6 7 3 13 25 24 16 17 37 18 23 22 21 C D 38 Section 8 Exploded Views and Parts Guardian Liquid cooled...

Страница 51: ...RETOR GASKET 21 076011 4 SCREW PRHM 10 24 X 1 2 22 022152 4 WASHER LOCK 10 23 023897 4 WASHER FLAT 10 ZINC 24 062522 1 STUD TH 1 4 20 X 3 G2 ZNC FULL 25 022127 1 NUT HEX 1 4 20 STEEL 26 022259 2 NUT H...

Страница 52: ...50 Generac Power Systems Inc Section 8 Exploded Views and Parts Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Exploded View Engine Compartment Drawing No 0A7642 J...

Страница 53: ...INTAKE 38 057522 1 SENSOR COOLANT LEVEL ITEM PART NO QTY DESCRIPTION 39 0A6751 1 SW TMP 245DEG 3 8NPT 40 034339 1 BARBED EL 90 3 8NPT X 5 8 41 0D4788 1 PLUG STD PIPE 3 8 STEEL SQ HD 42 061012 1 PLUG S...

Страница 54: ...52 Generac Power Systems Inc Section 9 Installation Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Installation Drawing 15 20 kW Drawing No 0A7214 C...

Страница 55: ...Generac Power Systems Inc 53 Section 9 Installation Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Installation Drawing 15 20 kW Drawing No 0A7214 C Air Intake Air Intake Air Outlet...

Страница 56: ...54 Generac Power Systems Inc Section 9 Installation Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Installation Drawing 25 kW Drawing No 0C1450...

Страница 57: ...Generac Power Systems Inc 55 Section 9 Installation Guardian Liquid cooled 15 kW 20 kW and 25 kW Generators Installation Drawing 25 kW Drawing No 0C1450 Air Intake Air Intake Air Intake...

Страница 58: ...any and or all warranty coverage or responsibility if your engine or a part component thereof has failed due to abuse neglect improper maintenance or unap proved modifications or the use of counterfe...

Страница 59: ...ion 4 below Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point f...

Страница 60: ...sting due to the improper installation location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised Failures caused by any contaminated fuels oils coolants...

Отзывы: