3.17 ADJUSTMENTS ON INPHASE
MONITOR CONTROL CIRCUIT BOARD
The Inphase Monitor Control board is operational only
when the generator set is running and producing elec-
tricity. Transfer will occur when UTILITY and GENER-
ATOR voltage and phase are comparatively equal with a
maximum difference of 20° between the power sources.
To assure precision matching control, minimum voltage
and frequency ranges are specified by the operator. In
addition, each inphase control is programmed with the
use of an onboard DIP switch to match the actuation
time of the corresponding switch. Inphase transfer is
used only between two live power sources and NOT dur-
ing a UTILITY source failure. The Inphase Monitor
Control board (Figure 3.13) is designed to transfer
loads under the following conditions:
• When generator set frequency is between 58-62 Hz
(48-52 Hz for 50 Hz systems).
• When generator set and utility power source frequen-
cies are within 2 Hz.
• When the generator set and utility source voltage are
within 85-100 percent of normal voltage.
• When both power sources are able to come into phase
within 10 seconds.
• When less than 10 seconds has elapsed since the
engine warmup timer has indicated “go ahead.”
If any one of the preceding conditions are not met with-
in 30 seconds, the system will automatically revert to
Time delay Neutral (if selected). If Time Delay Neutral is
not selected, the switch will transfer immediately after
failing to do an inphase transfer within the 30 second
window.
3.17.1 ENGINE WARMUP TIMER
Permits the engine to warm up before transferring
LOAD from NORMAL to STANDBY power. Reset timer
to any time interval between 5 seconds and 3 minutes;
factory set to about 1 minute.
3.17.2 ENGINE MINIMUM RUN TIMER
Establishes the minimum length of time the generator
must run before it can be shut down automatically.
Timer prevents a cold engine from being shut down. It
is factory set to about 20 minutes, but you can reset the
interval between 5 and 30 minutes.
3.17.3 RETURN TO UTILITY TIMER
Establishes time interval between restoration of NOR-
MAL source voltage above the setting of the Voltage
Pickup Sensor and re-transfer back to that source.
This time interval is necessary, to prevent re-transfer
that otherwise might occur as a result of transient volt-
ages. Timer may be reset to any interval between 1 and
30 minutes; factory set to about 5 minutes.
◆
◆
◆
Section 3 — Operation
Generac GTS “W” Type Transfer Switch
Figure 3.13 — Inphase Monitor Control Panel
COOLDOWN
ENGINE
RETURN
TO UTILITY
ENGINE
MINIMUM RUN
ENGINE
WARMUP
TRANSFER
TIME DELAY
FREQUENCY
NEUTRAL
SIGNAL
BEFORE
STANDBY
VOLTAGE
STANDBY
90821B
MIN
1
MIN
1
MIN
30
SEC
0.1
30
MIN
SEC
1
MIN
SEC
5
MIN
80%
30
MIN
5
3
SIGNAL
BEFORE
BYPASS
WARMUP
TRANSFER
TRANSFER
ON EXERCISE
OFF
SEC
10
SEC
30
ON
OFF
OFF
ON
ON
TDN TIMER
TRANSFERRED
STANDBY RUN
TO STANDBY
SIGNAL BEFORE
TRANSFER TIMER
SIGNAL
T
R
CALIBRATION
SELECT
TRANSFER
INPHASE
N
O
C
T
90%
OFF
ON
STDBY
OFF
UTIL
MODE
85%
95%
N
M
I
N
O
I
H
P A
O L
RETURN TO
TIMER
SELECTED
INPHASE
TRANSFER
COOLDOWN
TIMER
UTILITY TIMER
TIMER
WARMUP
MINIMUM RUN
R
O
E
S
Содержание GTS "W"
Страница 25: ...Generac Power Systems Inc 23 Section 5 Notes Generac GTS W Type Transfer Switch...
Страница 26: ...24 Generac Power Systems Inc Section 5 Notes Generac GTS W Type Transfer Switch...
Страница 27: ...Generac Power Systems Inc 25 Section 5 Notes Generac GTS W Type Transfer Switch...
Страница 42: ...40 Generac Power Systems Inc Section 8 Exploded Views Parts Lists Assembly Drawing No 0D7651 C Part 1...
Страница 44: ...42 Generac Power Systems Inc Section 8 Exploded Views Parts Lists Assembly Drawing No 0D7651 C Part 2...
Страница 46: ...44 Generac Power Systems Inc Section 8 Exploded Views Parts Lists Assembly Drawing No 0D7651 C Part 3...
Страница 49: ...SCHEMATIC DIAGRAM DRAWING PAGE 1 OF 1 DATE GROUP UTILITY INTERFACE GTS 0676170700 G 8 4 04 REVISION G 3440 C...
Страница 50: ......
Страница 52: ......
Страница 54: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......