OPERATING DATA
GR160
STANDBY
PRIME
GR160
GR160
GENERATOR OUTPUT VOLTAGE/KW-60HzSTANDBY
240V, 1-phase, 1.0 pf
kW
133
126
120/208V, 3-phase, 0.8 pf
kW
133
126
139/240V, 3-phase, 0.8 pf
kW
133
126
277/480V, 3-phase, 0.8 pf
kW
133
126
AMPERAGE
Single phase 240V
Amps
554
525
Three phase 208V
Amps
461
437
Three phase 240V
Amps
400
379
Three phase 480V
Amps
200
189
MOTOR STARTING KVA
416V
480V
416V
480V
Maximum at 35% instantaneous voltage dip
60 Hz - kVA
680
950
680
950
FUEL
Fuel consumption 60 Hz
Load
25%
50%
75%
100%
25% 50% 75% 100%
gal/hr
4.4
6.6
8.8
9.3
3.5
5.3
7.0
7.4
liters/hr
16.7
25.0
33.3
35.2
13.4
20.0
26.6 28.2
COOLING
Coolant capacity
System lit (US gal)
22 (5.8)
22 (5.8)
Engine lit (US gal)
14 (3.7)
14 (3.7)
Radiator lit (US gal)
8 (2.1)
8 (2.1)
Coolant flow/min.
60 Hz - lit (US gal)
270 (71.3)
270 (71.3)
Heat rejection to coolant
BTU/hr
344,000
309,600
Inlet air
60 Hz - cu meters/min (cfm)
120 (4500)
120 (4500)
Max. inlet air temperature
°F
110
110
COMBUSTION AIR REQUIREMENTS
Flow at rated power
60 Hz - cu meters/min (cfm)
8.9 (314)
8.0 (283)
EXHAUST
Exhaust flow at rated output 60 Hz cu meters/min (cfm)
31.6 (1115)
28.4 (1003)
Maximum recommended back pressure Kpa ("H
2
O)
7.5 (30)
7.5 (30)
Exhaust temperature at rated output
°C (°F)
496 (925)
446 (835)
ENGINE
Rated RPM
60 Hz
1800
1800
Rated HP
60 Hz
194
175
Piston speed
60 Hz - m/min (ft/min)
464 (1524)
464 (1524)
BMEP (psi)
60 Hz
171
155
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature
-3% for every 10°C above - °C
25
25
-1.5% for every 10°F above - °F
77
77
Attitude
-3.0% for every 300 m above - m
1523
1523
-3.0% for every 1000 ft above - ft
5000
5000