Maintenance
Owner’s Manual for 60 Hz Air-Cooled Generators
31
Return to Service
Proceed as follows to return the unit to service after
storage:
1.
Check the tag on the engine for oil viscosity and
classification. Drain and fill with proper oil, if
necessary.
2.
Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled
water. DO NOT use tap water. Recharge the
battery to 100% state of charge. Replace the
battery if defective.
3.
Clean and wipe down the entire generator
enclosure.
4.
Verify the 7.5 A fuse is removed from the generator
control panel.
5.
Connect the battery.
6.
Connect the battery charger AC input T1/Neutral
cable (has white sleeve) at controller.
NOTE:
The exercise timer and current date and time
must be reset when a battery is dead or has been
disconnected.
7.
Open the fuel shutoff valve.
8.
Insert the 7.5 A fuse into the generator control
panel.
9.
Complete the Installation Wizard information.
10.
Press the MANUAL mode button to start the unit.
Allow the unit to warm up for a few minutes.
11.
Press the control panel OFF mode button to stop
the unit.
12.
Set the MLCB (generator disconnect) to ON
(CLOSED).
13.
Press the AUTO mode button on the control panel.
The generator is ready for service.
(000133)
WARNING
Explosion. Batteries emit explosive gases.
Always connect positive battery cable first to
avoid spark. Failure to do so could result in
death or serious injury.