Generac Power Systems CTTS Series Скачать руководство пользователя страница 2

2 of 2

Generac Power Systems, Inc. • S45 W29290 HWY. 59,  Waukesha, WI 53189 • generac.com

©2010 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0164210SBY-A / Printed in U.S.A. 01/06/11

100 - 400 Amps, 600 VAC

Terminal Lug Wire Ranges

Withstand Current - 600 Volt CTTS Series

Mechanical Dimensions (NEMA 1, Standard)

CTTS Control Systems

LOGIC CONTROL w / Inphase Monitor

Utility Voltage

 

Dropout (% of pickup) ............................................................................................75-95% (Adj.)

 

Pickup ....................................................................................................................85-95% (Adj.)

 

Line Interrupt ......................................................................................................0.1-10 Sec. (Adj.)

Engine Minimum Run ......................................................................................................... 5-30 Min. (Adj.)

Engine Warmup............................................................................................................... 5 Sec.-3 Min. (Adj.)

Return to Utility .................................................................................................................. 1-30 Min. (Adj.)

Engine Cooldown ............................................................................................................... 1-30 Min. (Adj.)

Standby Voltage ...................................................................................................................85-95% (Adj.)

Standby Frequency ..............................................................................................................80-90% (Adj.)

Time Delay Neutral ...........................................................................................................0.1-10 Sec. (Adj.)

Transfer on Exercise ............................................................................................................On/Off Switch

Warmup Timer Bypass .........................................................................................................On/Off Switch

Time Delay Neutral When Fail to Syng .................................................................................On/Off Switch

GTS Rated Amps 

100 

150 

200 

300 

400

Fuse Protected

  Maximum RMS Symmetrical

  Withstand Current  

200,000 

200,000 

200,000 

200,000 

200,000

Protective Device Continuous

  Rating (Max) Amp 

200 

400 

400 

600 

600

Fuse Class 

J,T 

J,T 

J,T 

J,T 

J,T

Circuit Breaker Protected

  Maximum RMS Symmetrical

  Withstand Current  

14,000 

25,000 

25,000 

35,000 

35,000

Protective Device Continuous

  Rating (Max) Amp 

150 

300 

300 

600 

600

*  Tested per UL 1008 and CSA Standards
*  Current ratings are listed @ 480 VAC

 

Current 

Height 

Width 

Depth 

Weight

Rating 

H1 

H2 

W1 

W2 

 

(lbs.)

100 

36.8 

37.5 

18 

24.8 

10 

180

150 

48.8 

49.5 

24 

30.75 

12 

265

200 

48.8 

49.5 

24 

30.75 

12 

265

300 

48.8 

49.5 

24 

30.75 

12 

325

400 

48.8 

49.5 

24 

30.75 

12 

325

GTS Rated Amps 

Switch Terminal 

Neutral Bar 

 

Ground Lug

100 

1X-2/0-14 

4X-2/0-14 

 

1X-2/0-14

150 

1X-400MCM-4 

4X-350MCM-6 

 

1X-350MCM-6

200 

1X-400MCM-4 

4X-350MCM-6 

 

1X-350MCM-6

300 

2X-250MCM-1/0 or 1X-600MCM-4  

8X-250MCM-1/0 or 4X-600MCM-4  1X-350MCM-6

400 

2X-250MCM-1/0 or 1X-600MCM-4 

8X-250MCM-1/0 or 4X-600MCM-4  1X-350MCM-6