Installation and Operating Instructions 

30A SWITCHED NEUTRAL ACCESSORY KIT MODEL 6297 

 

 

Warning: 

 This

 Switched Neutral Kit should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in 

working with generator transfer switches.  Generac accepts no responsibility for accidents, damages or personal injury caused by incorrect installation.  
The Switched Neutral Kit can upgrade most manual transfer switches from non-Switched neutral to Switched neutral, as required by certain 

municipalities, electrical inspectors and generators.   

Caution: 

 This Switched Neutral Kit can be used in single phase manual transfer switches up to 30 Amps 125/250V.  Check the transfer switch rating 

label BEFORE beginning installation to be sure NOT to exceed the rating of the transfer switch.  Incorrect or inappropriate installations will void the 
warranty.

 

 

For use with Neutral-Bonded Generators. This Switched Neutral Kit 
is designed to enable manual transfer switches up to 30 Amps @ 
125/250V to isolate the utility and generator neutrals.  Product 
features include: 

 

 

Preserve the integrity of your generator ground fault protection system 

by isolating the utility and generator neutrals. 

 

Generator and Utility neutrals are interlocked; neutral pole is 
simultaneously switched and connected to only one source at any time. 

 

Prewired for fast, easy connection to the transfer switch and load 
center. 

 

Retrofit most any make or model of manual transfer switch, load center 
or isolation device.  

 

All components are UL Listed and/or Recognized. 

 

What is Included in this carton: 

A.

 

Prewired Contactor, UL listed 

B.

 

Wire Harness 

C.

 

Wire Connectors (3) 

D.

 

Insulated terminal block, 8 position 

E.

 

Installation manual and Warranty Registration Card (this document) 

 

Tools Needed for Installation:  

 

Screwdrivers, straight blade and Phillips 

 

Wire cutter/stripper 

 

Safety eye goggles 

 

STEP 1:  PLANNING YOUR INSTALLATION: 

Look on the product label on your transfer switch to determine which model you have, and that it is rated for up to 30 amps.  You will need 

this information throughout this procedure.

 

 

STEP 2:  INSTALLATION PROCEDURE: 

 PLEASE READ THIS MANUAL 

BEFORE

 ATTEMPTING TO INSTALL, OPERATE OR MAINTAIN THIS EQUIPMENT.  HAZARDOUS VOLTAGES ARE PRESENT INSIDE 

TRANSFER SWITCH and LOAD CENTER ENCLOSURE THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY.  FOLLOW PROPER INSTALLATION, OPERATION AND 
MAINTENANCE PROCEDURES TO AVOID HAZARDOUS VOLTAGES.  

TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING INSTALLATION

.

 

 

 

A. Install contactor (Item A) into manual transfer switch: 

1.

 

Referring to Figure 1, determine the appropriate location to install the 
contactor inside the manual transfer switch enclosure, based upon the 
manual transfer switch model determined in STEP 1. Clean the location 
from all dirt and grease. Remove the double-stick tape backing on the 

contactor and press the contactor tight to the enclosure. Make sure that the 
wires attached to the contactor are accessible for routing and termination. 

B. Terminate NC1 and NC2 in load center (electrical panel): 

1.

 

Locate the 67” gray wires marked NC1 and NC2 connected to the 

contactor. For 6294 manual transfer switch, route, insert and feed both 