2.12 LOW OIL PRESSURE SHUTDOWN SYSTEM

The engine is equipped with a low oil pressure sensor that shuts 

down the engine automatically when the oil pressure drops below 

5 psi. A delay built into the low oil shutdown system allows oil 

pressure to build during starting. The delay allows the engine to 

run for about 10 seconds before sensing oil pressure. If the engine 

shuts down by itself and the fuel tank has enough gasoline, check 

engine oil level.

2.12.1 RESTARTING

If trying to restart the engine within 10 seconds after it shuts 

down, the engine may NOT start. The system needs five (5) to 10 

seconds to reset.
If the engine is restarted after such a shutdown and the low oil 

pressure has not been corrected, the engine will run for about 10 

seconds as described above and then stop.

2.13 CHARGING THE BATTERY

 Do not permit smoking, open flame, sparks 

or any other source of heat around a battery. 

Wear protective goggles, rubber apron and 

rubber gloves when working around a battery. 

Battery electrolyte fluid is an extremely 

corrosive sulfuric acid solution that can cause 

severe burns. If spill occurs flush area with 

clear water immediately.



 Storage batteries give off explosive hydrogen 

gas while recharging. An explosive mixture will 

remain around the battery for a long time after 

it has been charged. The slightest spark can 

ignite the hydrogen and cause an explosion. 

Such an explosion can shatter the battery and 

cause blindness or other serious injury.

Use battery charger plug to keep the battery charged and ready 

for use. Battery charging should be done in a dry location.

1.  Plug charger into “Battery Charger Input” jack, located on the 

control panel. Plug wall receptacle end of the battery charger 

into a 120 Volt AC wall outlet.

2.  Unplug battery charger from wall outlet and control panel jack 

when generator is going to be in use.

NOTE:

Do not use the battery charger for more than 48 hours at one 

charge.

3.1  PERFORMING SCHEDULED MAINTENANCE

It is important to perform service as specified in the Maintenance 

Schedule for proper generator operation, and to ensure that the 

generator complies with the applicable emission standards for the 

duration of its useful life. Service and repairs may be performed by 

any capable person or repair shop. Additionally, emissions critical 

maintenance must be performed as scheduled in order for the 

Emissions Warranty to be valid. Emissions critical maintenance 

consists of servicing the air filter and spark plugs in accordance 

with the Maintenance Schedule. 

3.2 MAINTENANCE SCHEDULE

Follow the calendar intervals. More frequent service is required 

when operating in adverse conditions noted below.
Check Oil Level 

At Each Use

Change Oil and Oil Filter‡ 

*Every Season/Every 100 Hours

Clean Spark Arrestor Screen 

*Every Season/Every 100 Hours

Service Air Filter 

*Every Season/Every 200 Hours

Replace Spark Plug 

*Every Season/Every 100 Hours

‡ 

Change oil after first 30 hours of operation then every season.

*   Change oil and oil filter every month when operating under heavy load or in 

high temperatures. Clean or replace more often under dirty or dusty operating 

conditions. Replace air filter parts if very dirty.

3.3 PRODUCT SPECIFICATIONS

3.3.1 GENERATOR 

SPECIFICATIONS

Rated Max. Power .................................................................10.0 kW**
Surge Power .............................................................................12.5 kW
Rated AC Voltage ......................................................................120/240
Rated Max AC Load
  Current @ 240V .............................................................41.6 Amps**
  Current @ 120V .............................................................83.3 Amps**
Rated Frequency .................................................... 60 Hz @ 3600 RPM
Phase ................................................................................ Single Phase
Rated DC Voltage ...................................................................... 12 Volts
Battery Type .................................................................... 10 AH, 12VDC

**  Maximum wattage and current are subject to, and limited by, such factors 

as fuel Btu content, ambient temperature, altitude, engine condition, etc.. 

Maximum power decreases about 3.5% for each 1,000 feet above sea level; 

and will also decrease about 1% for each 6° C (10° F) above 16° C (60° F) 

ambient temperature.

3.3.2 ENGINE 

SPECIFICATIONS

Rated Horsepower @ 3600 RPM ................................................. 18 Hp
Displacement ............................................................................... 530cc
Spark Plug Type ...........................................NGK BPR6HS or Equivalent
Spark Plug Gap ............................................... 0.030 inch or (0.76 mm)
Gasoline Capacity .......................................................... 10 U.S. gallons
Oil Type.................................... See Chart in "Adding Engine Oil" Section
Oil Capacity ................................................ w/ Filter Change = 1.8 Qts.
 

w/o Filter Change = 1.5 Qts.

Run Time/Fuel Consumption-1/2 Load .. 10 Hours / .73 gallons per hour
Class II Emission Certified

11

Maintenance

Содержание 005802-2 XG Professional Series

Страница 1: ...essional Series Portable Generator MODEL 005802 2 DEADLY EXHAUST FUMES ONLY use OUTSIDE far away from windows doors and vents NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS SAVE this Manua...

Страница 2: ...ery 11 Maintenance 11 3 1 Performing Scheduled Maintenance 11 3 2 Maintenance Schedule 11 3 3 Product Specifications 11 3 4 General Recommendations 12 3 5 Service Air Filter 13 3 6 Clean Spark Arresto...

Страница 3: ...efinitions are as follows INDICATES A HAZARDOUS SITUATION OR ACTION WHICH IF NOT AVOIDED WILL RESULT IN DEATH OR SERIOUS INJURY Indicates a hazardous situation or action which if not avoided could res...

Страница 4: ...or feet are wet DANGEROUS ELECTRICAL SHOCK MAY RESULT The National Electric Code NEC requires the frame and external electrically conductive parts of the generator be properly connected to an approve...

Страница 5: ...guideline for operation of this equipment Always reference the latest revision available for the standards listed 1 NFPA No 70 NFPA HANDBOOK OF NATIONAL ELECTRIC CODE 2 Article X NATIONAL BUILDING COD...

Страница 6: ...sembly prior to using it If problems arise when assembling the generator please call the Generator Helpline at 1 888 436 3722 1 2 1 ASSEMBLING THE WHEEL KIT AND FRAME FOOT The wheel kit is designed to...

Страница 7: ...0 Amp receptacle is protected with a push to reset circuit breaker to protect the generator against electrical overload The 50 Amp receptacle and one 30 Amp receptacle use toggle reset circuit breaker...

Страница 8: ...nance message four times until the meter resets itself 100 hours CHG OIL Oil Change Interval Every 100 hrs 200 hours SVC Air Filter Interval Every 200 hrs 2 3 CORD SETS AND CONNECTION PLUGS 2 3 1 120...

Страница 9: ...llation or permit even partial blockage of ventilation provisions as this can seriously affect safe operation of the generator The generator MUST be operated outdoors This exhaust system must be prope...

Страница 10: ...sure to allow for high starting wattage when selecting electrical devices to connect to the generator 1 Figure the watts needed to start the largest motor 2 Add to that figure the running watts of all...

Страница 11: ...light a cigarette or smoke when filling the fuel tank NEVER fill fuel tank indoors NEVER fill fuel tank when engine is running or hot Avoid spilling gasoline on a hot engine Allow engine to cool entir...

Страница 12: ...ration can be ensured by installing an altitude kit when required See the table below to determine when an altitude kit is required Operating this generator without the proper altitude kit installed m...

Страница 13: ...service as specified in the Maintenance Schedule for proper generator operation and to ensure that the generator complies with the applicable emission standards for the duration of its useful life Se...

Страница 14: ...ids and crevices of the rotor and stator winding insulation Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings 3 4 2 TO CLEA...

Страница 15: ...lter is too dirty replace it with a new one Dispose of the old filter properly Clean air filter cover Next insert new paper filter into the base of the air filter Re install air filter cover NOTE To o...

Страница 16: ...outer surfaces Check that cooling air slots and openings on generator are open and unobstructed Store the unit in a clean dry place 3 9 OTHER STORAGE TIPS Do not store gasoline from one season to ano...

Страница 17: ...12 Engine has lost compression 1 Turn Fuel shut off ON 2 Clean or replace air filter 3 Fill fuel tank 4 Drain fuel tank and fill with fresh fuel 5 Connect wire to spark plug 6 Replace spark plug 7 Dr...

Страница 18: ...a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem o...

Страница 19: ...ired maintenance in the Owner s Manual shall be warranted for the period of time prior to first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the...

Страница 20: ...lly exist Once a generator has experienced commercial or rental use it shall thereafter be considered a non consumer use generator for the purpose of this warranty GUIDELINES 1 All warranty repairs mu...

Страница 21: ...cceptable quality and the failure does not amount to a major failure For Service or other product inquiries in Australia please contact Allpower by phone at 1800 333 428 or visit Allpower s website at...

Страница 22: ...Manual Part No 0J2636 Revision D 06 18 13 Printed in U S A...

Страница 23: ...02 2 DE GARANT A LIMITADA DOS A OS DOS A OS PELIGRO HUMOS DE ESCAPE MORTALES Util celo SOLAMENTE al AIRE LIBRE y lejos de ventanas puertas y respiraderos NO DISE ADO PARA SER USADO EN APLICACIONES DE...

Страница 24: ...11 3 2 Programa de mantenimiento 11 3 3 Especificaciones del producto 11 3 4 Recomendaciones generales 12 3 5 Servicio del filtro de aire 13 3 6 Limpie el filtro del supresor de chispas 13 3 7 Genera...

Страница 25: ...ones son como sigue PELIGRO INDICA UNA SITUACI N PELIGROSA O ACCI N QUE SI NO SE EVITA TRAER COMO RESULTADO LA MUERTE O UN DA O SERIO ADVERTENCIA Indica una situaci n o acci n peligrosa que si no se e...

Страница 26: ...l equipo conectado al generador Aseg rese de que todas las cubiertas guardas y barreras adecuadas est n colocadas en su sitio antes de hacer funcionar el generador Nunca manipule ning n tipo de cable...

Страница 27: ...CE DE NORMAS En ausencia de las normas c digos reglamentos y leyes pertinentes la informaci n publicada que se lista a continuaci n puede utilizarse como pauta para la operaci n de este equipo Siempre...

Страница 28: ...ador al 1 888 436 3722 1 2 1 ENSAMBLE DEL KIT DE RUEDAS Y PATA DEL MARCO El kit de rueda est dise ado para mejorar grandemente la portabilidad del generador Usted necesitar las siguientes herramientas...

Страница 29: ...uito tipo presionar para reajustar para proteger al generador de sobrecargas el ctricas El recept culo de 50 amperios y uno de 30 amperios usan interruptores de circuito de reajuste de palanca El cort...

Страница 30: ...L CAMBIO DE ACEITE Intervalo de cambio de aceite Cada 100 horas 200 horas SVC Intervalo de filtro de aire Cada 200 horas 2 3 CABLES Y ENCHUFES DE CONEXI N 2 3 1 RECEPT CULO DOBLE GFCI 120 VAC 20 AMPER...

Страница 31: ...ser operado en exteriores Este sistema de escape debe tener un apropiado mantenimiento No haga nada que pueda poner en peligro la seguridad del escape o que no cumpla con alg n c digo local o est ndar...

Страница 32: ...ule la potencia que necesita el motor m s grande para arrancar 2 A ada a esta cifra los vatios de funcionamiento de todas las otras cargas conectadas La Gu a de Referencia de Potencia se proporciona p...

Страница 33: ...combustible en interiores NUNCA llene el dep sito de combustible cuando el motor est en marcha o caliente Evite derramar gasolina en un motor caliente Permita que el motor se enfr e totalmente antes d...

Страница 34: ...un kit de altitud cuando se requiera Vea la tabla de abajo para determinar cu ndo se requiere un kit de altitud La operaci n de este generador sin el apropiado kit de altitud instalado puede aumentar...

Страница 35: ...ctor hembra del panel de control cuando vaya a usar el generador NOTA No use el cargador de la bater a por m s de 48 horas en una carga 3 1 C MO REALIZAR MANTENIMIENTO PROGRAMADO Es importante realiza...

Страница 36: ...n objeto o herramienta a trav s de las ranuras de enfriamiento por aire incluso si el motor no est en funcionamiento NOTA NO utilice una manguera de jard n para limpiar el generador El agua puede entr...

Страница 37: ...el filtro de aire Retire la cubierta del filtro de aire y quite el papel de filtro Figura 13 Para limpiar el papel de filtro golp elo suavemente sobre una superficie dura Si el filtro est muy sucio re...

Страница 38: ...No conecte los cables de la buj a Limpie las superficies externas del generador Compruebe que las ranuras y aberturas del aire de enfriamiento en el generador est n abiertas y sin obst culos Almacene...

Страница 39: ...osici n ON 2 Limpie o reemplace el filtro de aire 3 Llene el tanque de combustible 4 Vac e el tanque de combustible y ll nelo con combustible nuevo 5 Conecte el cable a la buj a 6 Remplace la buj a 7...

Страница 40: ...iento inapropiado o modificaciones no autorizadas Usted es responsable de ponerse en contacto con un Centro de Garant a Autorizado de Generac tan pronto como ocurra un problema Las reparaciones por ga...

Страница 41: ...como parte del mantenimiento necesario en el Manual del Usuario ser garantizada por el periodo de tiempo previo al primer reemplazo programado para dicha pieza Si la pieza falla antes del primer reemp...

Страница 42: ...nt a no se aplica a las unidades usadas para alimentaci n principal en lugar de un servicio p blico donde hay servicio p blico de alimentaci n o donde el servicio p blico de alimentaci n normalmente n...

Страница 43: ...e consumidores Usted tiene derecho a sustituci n o reembolso por un fallo mayor y a compensaci n por cualquier otra p rdida o da o razonable previsible Usted tambi n tiene derecho a que los bienes sea...

Страница 44: ...N de parte del Manual 0J2636 Revisi n D 18 06 13 Impreso en EE UU...

Страница 45: ...part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications You are responsible for contacting a Generac Authorized Warranty Dealer as soon as a problem oc...

Страница 46: ...red maintenance in the Owner s Manual shall be warranted for the period of time prior to first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the...

Страница 47: ...nto inapropiado o modificaciones no autorizadas Usted es responsable de ponerse en contacto con un Centro de Garant a Autorizado de Generac tan pronto como ocurra un problema Las reparaciones por gara...

Страница 48: ...omo parte del mantenimiento necesario en el Manual del Usuario ser garantizada por el periodo de tiempo previo al primer reemplazo programado para dicha pieza Si la pieza falla antes del primer reempl...

Страница 49: ...de la garantie ou de la responsabilit si votre appareil et ou toute pi ce de celle ci ne fonctionne plus du fait d un usage abusif d une n gligence d une mauvaise maintenance ou de modifications non...

Страница 50: ...tien sera garantie pour la p riode pr c dant la date du premier remplacement pr vu Si la pi ce devient d fectueuse avant le premier remplacement pr vu elle sera r par e ou remplac e par Generac confor...

Отзывы: