Owner’s Manual for Mobile Generator
15
Section 3: Operation
Prestart Checklist
Before starting the unit, all items in the prestart checklist
must be completed.
•
Verify all maintenance procedures are up to date.
For more information, see
and
.
•
Verify the unit is level.
•
Verify there is no water inside, on, or near the unit.
Dry if needed.
•
For grounding requirements, follow any local, state,
or National Electrical Code (NEC) guidelines.
•
Verify the key switch is OFF (O).
•
Verify all circuit breakers are OFF (O).
•
Inspect all electrical cords; repair or replace any
that are cut, worn, or bare.
•
Verify oil, coolant, and fuel levels are correct, per
the engine manufacturer manual.
•
Verify battery connections are secure.
•
Turn the battery disconnect switch ON, if equipped.
•
Inspect the engine fan belt tension and condition.
•
Inspect the engine fan guard.
•
Inspect the engine exhaust system for loose or
rusted components.
•
Verify the radiator and surrounding shroud are
clear of debris.
•
Verify all covers are in place and secure.
•
Verify the emergency stop switch is pulled out.
Starting the Unit
NOTE:
If the engine was run out of fuel or the fuel tank
was drained, it may be necessary to bleed the fuel lines.
See the engine operator’s manual supplied with the unit.
1.
Verify the main circuit breaker and individual circuit
breakers for each of the receptacles are OFF (O).
NOTE:
When the circuit breaker indicator light
(
) is illuminated, the main circuit breaker must
be turned to OFF (O).
2.
See
. Turn the key on the key switch to
GLOW PLUG and hold for five seconds, or until the
glow plug indicator turns red.
Figure 3-1. Activate Glow Plug
NOTE:
For glow plug interval in cold weather conditions,
see engine manual.
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
Asphyxiation. Running engines produce
carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER
CAUTION
(000230)
Equipment Damage. Do not continuously crank
engine for more than ten seconds. Doing so will lead
to overdischarge of batteries and starter seizure.
003552
GLOW
PLUG
Содержание MLG15
Страница 4: ...Owner s Manual for Mobile Generator iv This page intentionally left blank ...
Страница 12: ...8 Owner s Manual for Mobile Generator Introduction and Safety This page intentionally left blank ...
Страница 26: ...22 Owner s Manual for Mobile Generator Maintenance This page intentionally left blank ...
Страница 28: ...24 Owner s Manual for Mobile Generator Troubleshooting This page intentionally left blank ...
Страница 34: ...30 Owner s Manual for Mobile Generator Wiring Diagrams This page intentionally left blank ...
Страница 35: ......