C. Factory RESET:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When VALUES appears, press the SELECT/FAST button. The 

display will rotate between SETUP, DIAG and RESET.

3.  When RESET appears, press the SELECT/FAST button. The 

display will rotate between YES or NO. 

4.  When YES appears, press the SELECT/FAST button.

Note: FACTORY RESET resets the transmitter back to its origi-
nal factory default settings: (20 mA = Minimum Range, 4mA = 
Maximum Range and SAFE = 22mA).

 

D. Testing the Transmitter

1.  Connect a multi-meter in transmitter with the black wire to read 

the current output. 

2.  Verify that the current increas-

es (tank filling) and decreases 
(tank emptying) appropriately 
in the calibrated span.

3.  If not, carefully observe and 

attempt to correlate any instal-
lation, level or application 
event for more specific trou-
bleshooting.

4.   Write down the information in 

DIAGNOSTICS (LEVEL, 
TEMP ECHO, POWER, 
MOUNT and VER) and have it 
ready when you contact your 
Gems representative.

Step Seventeen

Step Sixteen

SELECT

FAST

SELECT

FAST

SELECT

FAST

TROUBLESHOOTING

Transmitter

UCL-520

4 mA Setting

26.2’ (8m)

20 mA Setting

8” (20 cm)

Factory Set Points

Power

Supply

Power

Supply

20 mA

4 mA

mA

4

5

6

mA

19

20

21

Red

Black

Red

Black

TROUBLESHOOTING

A. Viewing Programmed VALUES:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When VALUES appears, press the SELECT/FAST button. The 

display will rotate between SETUP, DIAG and RESET.  

3.  When SETUP appears, press the SELECT/FAST button. You will 

now begin viewing calibration settings (UNITS, Display, MinR, 

MaxR and SAFE) that are programmed in the transmitter. 

When complete the display will revert back to the VALUES menu.

B. Viewing DIAGNOSTICS:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When VALUES appears, press the SELECT/FAST button. The 

display will rotate between SETUP, DIAG and RESET.  

3.  When DIAG appears, press the SELECT/FAST button. You will 

now begin viewing diagnostic values (LEVEL, TEMP ECHO, 

POWER, MOUNT and VER) that may be relevant to the trans-

mitter and it’s performance in your application.

When complete the display will revert back to the VALUES menu.

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

Содержание UCL-520

Страница 1: ...d include original packing slip C O D returns are not accepted Gems reserves the right to apply restocking charges Gems further reserves the right to unilaterally waive this warranty and to dispose of...

Страница 2: ...ut 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold last value Process temp F 4 to 140 C 20 to 60 Temp comp Automatic Electr...

Страница 3: ...iring and Electrical A supply voltage loop power of 12 28 VDC is used to power the UCL 520 transmitter The sensor circuit should never exceed a maximum of 28 volts DC Electrical wiring of the sensor s...

Страница 4: ...ort period of time this message will disappear and be replaced by a numeric value B FULL Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNIT...

Страница 5: ...POWER Displays the present acoustic power level AA MOUNT Displays either QUIET no fitting noise or NOISY potential fitting noise If NOISY with transmitter performance issues please contact Gems to di...

Страница 6: ...MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 When UNITS...

Страница 7: ...LECT FAST button The dis play will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the...

Страница 8: ...ique that allows the user to enter the present distance from the transducer face to the liquid or a reflective target as the 20 mA FULL set point EMPTY Target calibration technique that allows the use...

Страница 9: ...in a 2 5 cm riser 3 Stand Pipe A stand pipe may be used to dampen turbulence or separate surface foam Select a minimum 3 pipe for the stand pipe The pipe length should run the measure ment span Cut a...

Страница 10: ...FAST SELECT FAST SELECT FAST TROUBLESHOOTING Transmitter UCL 520 4 mA Setting 26 2 8m 20 mA Setting 8 20 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA 19 20 21 Red Black Red...

Отзывы: