RemoDAQ-9X20 Series User’s Manual
Station
Address
Start
Address
High
Byte
Start
Address
Low
Byte
Requested
Numberof
Register
High Byte
Requested
Numberof
Register
Low Byte
Function
Code
Example:
Read Analog inputs #1 and #2 in addresses 40001 to
40004 as floating point value from RemoDAQ-9X20.
01 04 00 01 00 04
Response message format for function code 03 or 04:
Command Body
Station
Address
Function
Data
Data
…
Byte
Code
Count
Example:
Analog input #1 and #2 as floating point values
where AI#1=100.0 and AI#2=55.32
01 04 08 42 C8 00 00 47 AE 42 5D
Function Code 05
Force a single coil to either ON or OFF. The requested
ON/OFF state is specified by a constant in the query data
field. A value of FF 00 hex requests it to be ON. A value
74