PROGRAMMING HEAT SET AND HUMIDITY SET
PROGRAMMING OTHER PARAMETERS
Gürbüzo
ğ
lu Elektronik San. ve Tic. Ltd.
Ş
ti.
http://www.gemo.com.tr
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye
e-posta: [email protected]
Tel: +90-312-3503900, Fax: +90-312-3511117
3
SET
SET
SET
Heat SET,
is set
t.Lo
..
t.UP
Press 2 sec.
Prog. end
Display
t.St
H.St
H.Lo ..
H.UP %RH
t.Lo .. t.UP
o
C
Humidity SET,
is set
H.Lo
..
H.UP
SET
0.1 .. 10.0
o
C
SET
t.St Hysteresis
value. (
o
C)
t.UP
SET
H.Ct
SET
+
Cod
Enter 162
SET
t.Lo
-19.9 .. t.UP
o
C
SET
t.St Lower Limit
value. (
o
C)
H.hS
SET
H.UP
H.Lo .. 95 %RH
SET
t.Ct=Ht
t.Ct
Ht, CL
SET
Ht: Heating Function
CL: Cooling Function
t.Os
-10.0 .. 10.0
o
C
SET
t.St Offset Value; Offset is directly
added to the measured value. This
feature shall be used for user calibration.
Normally set to 0. (
o
C)
H.Os
SET
t.St Upper Limit
value. (
o
C)
Enter 162 to pass to
Parameter prog. mode.
Display
H.Lo
5 .. H.UP %RH
SET
Delay time before
o
C OUT is ON. Active
only for cooling function is selected.
Press for 2 sec.
t.hS
t.Lo .. 80.0
o
C
-20 .. 20 %RH
dtr
SET
0..300 sec.
Prog. end
Scr
SET
FLS, St.t, St.H
Lo: Humidity Decrease Function
hi: Humidity Increase Function
H.St Hysteresis
value. (% RH)
H.St Upper Limit
value. (% RH)
H.St Lower Limit
value. (% RH)
H.St Offset Value; Offset is directly
added to the measured value. This
feature shall be used for user calibration.
Normally set to 0. (% RH)
FLS:
o
C and % RH measured values are seen periodically
St.t:
o
C value is static after power on, may be switched
to % RH by pressing “DOWN” switch
St.H: % RH value is static after power on, may be switched
to
o
C by pressing “DOWN” switch
Lo, hi
1 .. 20 %RH
Factory SET Values:
t.St: 50.0
o
C
H.St: 60 %RH
t.Ct: Ht
t.hS: 0.5
o
C
t.UP : 80.0
o
C
t.Lo: -19.9
o
C
t.Os: 0.0
o
C
H.Ct: Lo
H.hS: 3 %RH
H.UP: 95 %RH
H.Lo : 5 %RH
H.Os: 0 %RH
dtr: 25 sec
Scr: FLS