GEMO
LT102HT
ON/OFF TEMPERATURE and HUMIDITY CONTROLLER
Attention
High Voltage,
Double / Reinforced NOT
CE Mark
Risk of Danger,
Risk of
Insulation
Litter
Warning
Electric Shock
TECHNICAL SPECIFICATION
•
Dimensions
: 35x77mm
•
Panel Cut-out
: 29x71mm
•
Display
: 3 Digits 7 Segment
•
Sensor Type
: Custom Sensor (GM-HT-01)
•
Measuring Scale
: -19,9..+80,0
o
C, 5 .. 95%RH
•
Resolution
: ± 0,1
o
C, ± 1%RH
•
Accuracy
: ± % 1 (
o
C), ± % 3 (%RH); (Over full scale)
•
Control Form
: ON-OFF
•
Heating / Cooling
: Ht (heating), CL (cooling); selectable
•
Humidity Function
: lo (decrease humidity), hi (increase humidity); selectable
•
o
C
Output
: Relay (NO + NC), 250VAC, 2A, Resistive load
•
%RH Output
: Relay (NO), 250VAC, 2A, Resistive load
•
Supply Voltage
: 100..240VAC, 50-60Hz or 24VDC/AC.
•
Power Consumption : < 6VA
•
Humidity
: 80% up to 30
o
C, then linearly decreases to 50% at 50
o
C (non-condensing)
•
Altitude
: < 2000 m
•
EMC
: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)
•
Safety
: EN 61010-1; Pollution degree 1, measurement category
I
, (Only light industrial
environment, double/reinforced isolated, non-conductive pollution environment)
•
Protection Class
: IP20; according to EN 60529
•
Operation Temp.
: 0 .. 50
o
C
•
Storage Temperature : -10
o
C .. 60
o
C (no icing)
•
Weight
: < 0.5 kg
•
Keys
: Micro switch
•
Torque for screwing : Max. 0.5 N.m
Error Message:
•
“Err”
: In case of measurement failure, “Err” message displayed and Relay
outputs become OFF
WARNING: Connect Humidity/Temperature sensor while power is off. Pay attention to the cable color codes
printed on the device label. Wrong connection may result permanent device/sensor failure.
no: normally open nc: normally closed
Gürbüzo
ğ
lu Elektronik San. ve Tic. Ltd.
Ş
ti.
http://www.gemo.com.tr
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye
e-posta: [email protected]
Tel: +90-312-3503900, Fax: +90-312-3511117
1