TECHNICAL SPECIFICATION

Dimensions

: DTH9:96x96, DTH7:72x72, DTH4:48x48, DTH2:35x77mm

Panel Cut-out

: DTH9:91x91, DTH7:68x68, DTH4:46x46, DTH2:29x71mm

Display

: 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)

Sensor Type

: J,K,T,S,R type T/C, Pt100 selectable

Measuring Scale

: -100..600 

o

C, J type T/C (Inpt=J),    -100.0 .. 600.0 

o

C, J type T/C (Inpt=J.0)

 -100..1300 

o

C, K type T/C (Inpt=k),  -100.0..999.9 

o

C, K type T/C, (Inpt=k.0)

 -100..400 

o

C, T type T/C (Inpt=t),     -100.0 .. 400.0 

o

C, T type T/C (Inpt=t.0)

  0..1750 

o

C, S type T/C (Inpt=S)        0 .. 1750 

o

C, R type T/C (Inpt=r)

 -100..600 

o

C, Pt100, (Inpt=Pt)          -100.0 .. 600.0 

o

C, Pt100, (Inpt=Pt.0)

Resolution

: ± 1

 o

C or ± 0.1

 o

C

Accuracy

: ± 1 % (Over full scale)

Control Form

: ON-OFF or P, PI, PD, PID - selectable

Control Output

: Relay, 250VAC, 2A, resistive load / SSR (12Vdc, 20mA) - selectable

Heat SET

: Lower Limit .. Upper Limit 

o

C (H.Set)

Heat Hysteresis

: 0 .. 50 / 0.0 .. 50.0 

o

C (H.hys); PID is active if set to 0

Proportional Band

: 5 .. 150 

o

C (Pb.C)

Integral Time

: 0:00 .. 30:00 min:sec. (OFF if set to 0:00)

Derivative Time

: 0:00 .. 10:00 min:sec. (OFF if set to 0:00)

Control Period

: 1 .. 200 sec. (Ct)

Offset

: -100..+100 

o

C / -100.0 .. +100.0 

o

C (oFFS)

Heating/Cooling

: Only heating function

Cold. Junc. Comp.

: 0 .. 50 

o

C (T/C)

Line Comp.

: 10 Ohm max. (3 wire Pt100)

Sensor Failure

: OUT output is active according to P.Err and Ct parameters in case of

 sensor failure, measurement out of range or hardware fails to measure
 input signal (OUT output is OFF if Perr is 0). 

Supply Voltage

: 100..240VAC, 50-60Hz - or
  (Optional; 24VDC/AC, maximum isolation voltage: 40VAC)

Power Consumption

: < 8VA

Humidity

: < 70% (non-condensing)

Altitude

: < 2000 m

EMC

: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)

Safety

: EN 61010-1; Pollution degree 2, measurement category 

II

  

(Only light industrial environment, double/reinforced isolated)

Protection Class

: IP20; according to EN 60529

Temperature Spec.

: Operating: 0 .. 50 

o

C, Storage -10

o

C .. 60

o

C (no icing)

Weight

: < 0.5 kg

Torque for screwing

: Max. 0.5 N.m

WARNING:

 if 2 wire Pt100 is used, connect compensation

lead to measuring lead:(DTH9:

17-18

, DTH7: 

13-14

,

DTH4: 

10-11

, DTH2: 

9-10

)

Отзывы: