OPERATING FAULTS
Note :
- The
last 5 working faults
are accessible through
the QAA 73, from LMU version 3.00, lines 728 /
729 / 730 / 731 / 732. The last saved fault code is
displayed at line 728.
Flame failure while the boiler is operating
Check and adjust the gas valve, check the
ionisation electrode and the connections,
possible live-neutral inversion of the
transformer supply
Poor air supply
Check the ventilator and the air inlet
Maximum flue gas temperature exceeded
Check whether the boiler is not on thermal
overload or that the exchanger is not clogged
Safety device activated
Check that shunt X10-03 is present and that
the wires are properly connected
No flame formed after the safety time
period
Check that the gas reaches the boiler (Pi),
check the condition of the gas valve, if there
is a major adjustment fault on the gas valve,
check the condition of the transformer,
cables, ignition electrode, ionisation current
value
Segment number or unauthorised
addressing on LPB or LMU
Check the addressing consistency
Incompatibility between the LMU and LPB
Check the addressing consistency
New LMU configuration
Check the b0 internal code
LMU setting error
Check the b0 internal code
The boiler is blocked
Press Reset to clear the message
Violation of the plausibility criteria (STB
related criteria)
Check the value of the criteria related to the
boiler overheating security
The minimum speed threshold of the fan
is not reached
Check the wiring of the fan and LMU, ensure
that the fan is turning correctly
The maximum speed threshold of the fan
is exceeded
Check the mains supply and the fan cable
connections
The service function is active
-
The regulator shut-down function is active
-
The boiler is in setting mode
This appears after one or more settings are
loaded either by the QAA73 or by the PC
TOOL. This means that a reset is necessary
to validate the new setting(s) and for the
boiler to return to normal operating.
Modem function is active
-
"Controlled screed drying" function is
active
-
Display A0
Description
Solution