Figure 2 is an example of the test decision tree and statements you can make based on the test results. It is
based on a detector with the stated sensitivity of 3.0± 0.5 %/ft.
Figure 2, Example of Test Decision Tree and Statement of Results
Start
Test
3.0
Alarm
A
Test
2.5
Test
3.5
Alarm
Alarm
Alarm
Alarm
Test
3.9
Test
1.0
Test
2.1
B
C
D
E
G
J
Alarm
F
H
Yes
No
No
Yes
Yes
Yes
No
No
Yes
Yes
No
Statement
Alarm at
Not Alarm at Statement of Test Results
A 3.0
%/ft
Is within manufacturer's specification of 3.0
±
0.5%/ft
B
3.0 %/ft
2.5 %/ft
Is within manufacturer's specification of 3.0
±
0.5%/ft
C
3.0 %/ft and 2.5 %/ft
Is within manufacturer's specification of 3.0
±
0.5%/ft
D 2.5
%/ft
2.1 %/ft
Is within manufacturer's specification of 3.0
±
0.5%/ft
E
3.5 %/ft and 3.0 %/ft
Is within manufacturer's specification of 3.0
±
0.5%/ft
F
2.1 %/ft
Is a borderline case. Outside manufacturer's specification.
Within test error
G
3.9 %/ft
Is a borderline case. Outside manufacturer's specification.
Within test error
H
3.9 %/ft
Is above the upper limit of manufacturer's specification and
outside of test error
J
At or below 1.0%/ft
Is outside of the manufacturer's range. Subject to false alarm