11.4.36 Analog output
The analog output function can be set with the
Analog Output
parameter.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0xBA
1
0
R/W
1 bit
Analog output
Direction
Boolean
0
0
1
2
8
R/W
2 bits
Type
uint:8
1
0
1
2
3
16
R/W
16 bits
Min.
uint:16
0
0 to Max
(0.0% to Max)
4
32
R/W
16 bits
Max.
uint:16
1000
Min to 1000
(Min to 100%)
Description of parameter values
Index name
Parameter
Values
Description
Analog output
Direction
0
1
Specify direction of the set value output.
0 = Rise (rising)
1 = Fall (falling)
Type
0
1
2
Determine signal output.
0 = 0 to 20 mA
1 = 4 to 20 mA
2 = 0 to 10 V
Min.
0 to Max
(0.0% to Max)
Determine minimum value of the output.
Max.
Min to 1000
(Min to 100%)
Determine maximum value of the output.
11.5 Events
The following IO-Link events can be transmitted.
Event
Mode
Type
Code
Device Hardware Fault
App/Disapp
Error
0x5000
Motor Unable To Move
App/Disapp
Error
0x8CE0
Device Temperature Over-Run
App/Disapp
Warning/Error
0x4210
Emergency Power
App/Disapp
Warning
0x5100
Primary Supply Voltage Under-Run
App/Disapp
Error
0x5111
Potifail Close
App/Disapp
Warning
0x8CA5
Potifail Open
App/Disapp
Warning
0x8CA4
Description – Events
Event
Description
Possible cause
Troubleshooting
Device Hardware Fault
0x5000
The event occurs when a hard-
ware fault is detected.
Fault in valve position detec-
tion.
Contact GEMÜ Support
Parameter can no longer be
read when switching the
device on.
Motor Unable To Move
0x8CE0
The event occurs when the
motor is blocked.
Valve is blocked (for example,
solid stuck in valve).
Check valve
Carry out initialization if valve
is OK
Valve corroded (rusted in
place).
GEMÜ R639 eSyStep
Positioner (Code S0)
www.gemu-group.com
51 / 63