P-SK-PSU320-24 2018.02.23
PSU320-24
Input:100~240VAC 1.2A 50/60Hz
Output:27.6VDC 2A (MAX.48W)
Charge:27.6VDC 0.25A (MAX.6W)
Battery Charger (Not included):
- Battery charger output is protected by polyswitch PPTC fuse to prevent
reverse polarity, short circuit, and low voltage.
Operation Instructions:
Please refer to the wiring diagram on the left. When the emergency signal input
(JW1, JW2) is triggered, the relay contacts will switch from NC to NO, cutting
power to the electrified lock, and simultaneously the buzzer will sound.
It is suggested to connect with fail-safe electromagnetic lock.
Fail-Safe
Electromagnetic Lock
Fail-Secure
Electric Strike
Call Point
Fire Panel/Smoke
Detector
Battery
Charger
24VDC-TBI
Input Voltage: 110~240VAC 50/60Hz
Output Voltage: 24VDC (Datum Point: 27.6VDC)
Output Current: 24VDC/2A (MAX.48W)
ALARM Output Voltage:24VDC (Datum Point: 27.6VDC)
LED Indicators:
AC Light: AC input is valid when light is on.
DC Light: DC output is valid when light is on.
Battery Light: Battery charger output is valid when light is
on and off when any of the following causes occurs:
1.Battery charger output is invalid. 2. Battery is damaged.
3. Battery voltage is low. 4. Battery is discharging.
PSU320-24 Electrical Specifications:
- Charging Time: Approximately 48 hours
DC Output: Each output is protected by a polyswitch PPTC fuse to
prevent overvoltage, overcurrent, and short circuit.
SWITCHING
AC INPUT
POWER SUPPLY
BATTERY
Power Supply Unit
PSU320-24
N.C COM. N.O ALARM
DC OUT BATTERY
TRIGGER
JW1 JW2
L
N
AC
DC
LED INDICATOR
AC Input “N”
AC Input “L”
12/24VDC
PPTC
Resistance
LED 2
LED 1
12/24VDC
Input Terminals
Terminals
Output
- Battery Type: Rechargeable sealed lead acid 7A/Hour@24VDC (12VDCx2)
EMERGENCY