INSTALLATION

NOTE

Residential Fire Sprinkler Sys-

tems should only be designed and

installed by those competent and

completely familiar with auto-

matic sprinkler system design, in-

stallation procedures, and tech-

niques.

The Model F993 Aquarius RES/QR-
EC/EC Horizontal Sidewall Sprinklers
must be installed in accordance with
the following instructions.

1. The Sprinkler must only be installed

in the sidewall, flush position with the
centerline of the waterway horizon-
tal and perpendicular to the mount-
ing surface.

NOTE

It is recommended that a spirit

level be used to level the sprin-

kler fitting as shown in Figure F

and that a square be used to

check perpendicularity of the

waterway centerline to the

mounting surface.

2. When using the Push-on Escutch-

eon Plate shown in Figure C, the
pipe connected to the sprinkler fitting
should be cut so that the “A” dimen-
sion is between 1 and 1-1/8 inches.
When using the Push-on Escutch-
eon Plate with Extension shown in
Figure D, the pipe connected to the
sprinkler fitting should be cut so that
the “A” dimension is between 13/16
and 1-1/16 inches. In either case,
the remaining portion of the adjust-
ment can be used to help compen-

sate for the possible manufacturing
variations in the make-in of  the
Sprinklers and the take-out of the
fittings (as permitted by ANSI
B1.20.1).

NOTE

The Push-on Escutcheon Plates

shown in Figures C and D can

NOT be used to hold the Sprin-

kler in position. The Sprinkler

must be secured in position by

firmly fastening the sprinkler

system piping to the dwelling

structure. If the Sprinkler is not

properly secured in position, re-

action forces resulting from

sprinkler operation could alter

its orientation and water distri-

bution pattern.

3. With pipe thread sealant applied to

the pipe threads, hand tighten the
Sprinkler with the attached Protec-
tive Cap (as shipped), into the sprin-
kler fitting.

4. Using the Model F873 Sprinkler

Wrench shown in Figure G, tighten
the  Sprinkler  into  the fitting. The
word “TOP”  on the Deflector Hat
must face upwards towards the ceil-
ing.

The Wrench is slipped over the Pro-
tective Cap and can be mounted to
a 1/2 inch socket drive ratchet. A
radial force of 10 to 18 lbs. applied
to a typical 9 inch long ratchet handle
will exert the 7 to 14 ft.lbs. of torque
required for a leak tight sprinkler
joint.

NOTES

It is recommended that a spirit

level be used to level the Deflec-

tor Hat, as shown in Figure F.

A maximum of 21 ft.lbs. of

torque is to be used to install the

sprinkler. Higher levels of

torque may distort the sprinkler

orifice seat with consequent

leakage.

5. Do not remove the Protective Cap at

this time. The Protective Cap is in-
tended to help protect the sprinkler
until the wall finish is complete and
the sprinkler system is ready to be
put into service.

NOTE

Failure to use the Protective

Cap, while the wall installation

is being completed, can result in

the accidental damage or paint-

ing of a sprinkler. Damaged or

painted sprinklers must be re-

placed.

6. After the wall finishing is complete

and the sprinkler system is ready to
be put into service, slide off the Pro-
tective Cap.

NOTE

Failure to remove the Protective

NOTES

:

1. For a given position within the coverage area, ceiling mounted obstructions must not hang

below the elevation dimension given in the graph.

2. Elevation dimensions are with respect to the top of the Deflector Hat (ref. Fig. A), where

positive (+) dimensions are above the Deflector Hat and negative (-) dimensions are below.
(Reference: the Deflector Hat is 5/8" above the sprinkler centerline of waterway.)

FIGURE E

ALLOWABLE ELEVATION FOR CEILING MOUNTED OBSTRUCTIONS

SUCH AS HEATING OR AIR CONDITIONING DIFFUSERS, OVERHANGS,

AND LIGHT FIXTURES

—5—

FIGURE F

LEVELING OF

SPRINKLER FITTING

AND DEFLECTOR

FIGURE G

MODEL F873

SPRINKLER WRENCH

OBSOLETE

Содержание AQUARIUS F993

Страница 1: ...e and the additional 1 4 inch of adjustment that can be obtained by use of the Exten sion reduces the accuracy to which the sprinklers must be positioned The 3 inch outside diameter of the Push on Pla...

Страница 2: ...ontal Side wall Sprinklers are available in a 160 F 71 C temperature rating and they are rated for use at a maximum service pressure of 175 psi They are available with a chrome white or bright brass f...

Страница 3: ...mum amount of water which must be discharged from an operat ing sprinkler the maximum area which can be covered by the spray from an oper ating sprinkler installation requirements necessary to the pro...

Страница 4: ...be located above an elevation as shown in Figure E where they will not inter fere with the proper distribution of water by the sprinkler The F993 Sprinklers must NOT be lo cated a along wall overhang...

Страница 5: ...inkler with the attached Protec tive Cap as shipped into the sprin kler fitting 4 Using the Model F873 Sprinkler Wrench shown in Figure G tighten the Sprinkler into the fitting The word TOP on the Def...

Страница 6: ...e re placed The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards...

Страница 7: ...stated under WARNINGS Alter the new construction and or the sprin kler system to suit the requirements of this document ORDERING PROCEDURE Orders for the Model F993 Aquarius RES QR EC EC Horizontal Si...

Страница 8: ...O B S O L E T E...

Отзывы: