GEM A/Q-71 Скачать руководство пользователя страница 2

of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration

of

chemicals,

and

gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.

APPROVALS AND STANDARDS

Laboratory listings and approvals for
the 5.6 K-Factor Model A/Q-71 Hori-
zontal Sidewall Sprinklers and Re-
cessed Horizontal Sidewall Sprinklers
are given in Table A.

WARNING

The 5.6 K-Factor Model A/Q-71 Hori-

zontal Sidewall Sprinklers and Re-

cessed Horizontal Sidewall Sprin-

klers described herein must be

installed and maintained in compli-

ance with this document, as well as

applicable standards of the National

Fire Protection Association, in addi-

tion to the standards of any other

authorities having jurisdiction. Fail-

ure to do so may impair the integrity

of these devices.
The owner is responsible for main-

taining their fire protection system

and devices in proper operating con-

dition. The installing contractor or

manufacturer should be contacted

relative to any questions.
Installation of Model A/Q-71 Hori-

zontal Sidewall Sprinklers in re-

cessed escutcheons other than the

F700 or F705 will void all sprinkler

warranties, as well as possibly void

the sprinkler’s Approvals and/or

Listings.

TECHNICAL DATA

The 5.6 K-Factor Model A/Q-71 Hori-
zontal Sidewall Sprinklers and Re-
cessed Horizontal Sidewall Sprinklers
are rated for use at a maximum service
pressure of 175 psi (12,1 bar). They
are to be installed in accordance with
the deflector-to-ceiling distance speci-
fications indicated in Table A, and the
standard rules recognized by the ap-

plicable  Listing or Approval agency.
The sprinklers are available in the tem-
perature ratings and finishes indicated
in Table A.

The nominal flow “Q” in GPM (LPM) is
determined by the following formula:

where the nominal discharge coeffi-
cient “K” equals 5.6 (80,7) and “p”
equals the residual flowing pressure in
psi (bar).

The Frame of the Model A Sprinkler
(Ref. Figure A), is a dezincification re-
sistant bronze, and the Deflector is
brass. The Button and Compression
Screw are bronze. The Gasketed
Spring Plate consists of a beryllium
nickel disc spring that is sealed on
both its inside and outside faces with
a Teflon

†

gasket. The quick response

Model A/Q-71 Sprinklers utilize a 3
mm diameter frangible bulb. Table A
indicates the bulb liquid color as a
function of temperature rating.

NOTES

Inquiries concerning the appropriate-

Q

K p

=

†

DuPont Registered Trademark

TYPE

TEMPERATURE

RATING

BULB

LIQUID

COLOR

NATURAL

BRASS

CHROME

PLATED

POLYESTER

COATED

(All Colors)

135°F/57°C

155°F/68°C

175°F/79°C

200°F/93°C

286°F/141°C

HORIZONTAL

SIDEWALL

(G7378)

SPRINKLER FINISH

Orange

Red

Yellow

Green

Blue

RECESSED

HORIZONTAL

SIDEWALL

(G7378)

WITH

F700

135°F/57°C

155°F/68°C

175°F/79°C

200°F/93°C

Orange

Red

Yellow

Green

NOTES:

1. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies.
2. Listed by Underwriters’ Laboratories of Canada as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies.
3. Approved by Factory Mutual Research Corporation as Quick Response Sprinklers for use in Light Hazard Occupancies.
4. Approved by the Loss Prevention Council (United Kingdom). The LPC does not rate the thermal sensitivity of horizontal sidewall

sprinklers.

5. Approved by the Scientific Services Laboratory (Australia) as Quick Response Sprinklers.
6. Accepted by the City of New York under MEA 241-94-E as Quick Response Sprinklers.
7. UL and ULC Listings, as well as FM, SSL, and NYC Approvals, are based on a deflector-to-ceiling distance of 4 to 12 inches (100 to

300 mm), whereas LPC Approval is based on 4 to 6 inches (100 to 150 mm). The top of the Deflector Hat, to which these dimensions
apply, is 9/16 inch (14.3 mm) above the centerline of waterway (Ref, Figure A).

N/A: Not Available

TABLE A

LABORATORY LISTINGS AND APPROVALS

(See Note 7 Above)

LEAD

COATED

N/A

1, 2, 3

1, 2, 4, 5, 6

1, 2, 3, 4, 5, 6

RECESSED

HORIZONTAL

SIDEWALL

(G7378)

WITH

F705

135°F/57°C

Orange

1, 2, 3, 4, 5, 6

N/A

155°F/68°C

Red

Yellow

175°F/79°C

200°F/93°C

Green

OBSOLETE

Отзывы: