12.3 Parameter overview
Index
Sub-
Index
Access
rights
Parameter
Function
Factory
settings
Setting options
0x02
0
W
System Command
Transmission of com-
mands for block para-
meterization and data
storage
0x01 to 0x06
0x82
0x03
1
R/W
Data Storage Cmd
Saving and restoring
parameter data for
device identical in
construction
2
RO
State Property
3
RO
Data Storage Size
4
RO
Parameter Checksum
5
RO
Index List
0x0C
1
R/W
Parameter (Write) Ac-
cess
Parameter Write Pro-
tection
0 → unlocked
1 → locked
2
R/W
Data Storage
Data Memory
0 → unlocked
1 → locked
3
R/W
Local Parameterization
Local Parameteriza-
tion
0 → unlocked
1 → locked
4
R/W
Local User Interface
Local User Interface
0 → unlocked
1 → locked
0x10
0
RO
Vendor Name
Read out manufacturer
name
"GEMUE"
0x12
0
RO
Product Name
Read out device name
"eSyStep Positioner"
0x15
0
RO
Serial Number
Read out serial num-
ber
"XXXXXXXX/YYYY"
0x16
0
RO
Hardware Revision
Read out hardware
version
"Rev. XX/XX"
0x17
0
RO
Firmware Revision
Read out software ver-
sion
"V X.X.X.X."
0x18
0
R/W
Application Specific Tag
Text with 32 charac-
ters can be entered
"****************"
0x19
0
R/W
Function Tag
Text with 32 charac-
ters can be entered
"****************"
0x20
0
R/W
Location Tag
Text with 32 charac-
ters can be entered
"****************"
0x40
0
RO
Actuator Size
Read out actuator size Depending on the
actuator size
used
0 → Actuator size 0
1 → Actuator size 1
2 → Actuator size 2
0x4B
1
R / W
Function digital input 1
Configure digital input
1
4
0 → Off
1 → Open
2 → Close
3 → Safe / On
4 → Init
2
R / W
Function digital input 2
Configure digital input
2
Code S0: 0
Code S5 / S6: 3
0 → Off
1 → Open
2 → Close
3 → Safe / On
4 → Init
0x4C
1
R/W
Function digital input/
output
Configure digital in-
puts/outputs
2
0 → Output Open
1 → Output Close
2 → Output Error
3 → Output Error &
Warning
4 → Input Init
www.gemu-group.com
36 / 64
GEMÜ 543
Positioner (Code S0)
12 Specific data IO-Link (pin 6)