27
80961F_MSW_GTF/GTF-Xtra_07-2018_ENG
VIRTUAL INSTRUMENT CONTROL
42
hd.1
R/W
Type of operation
0
Table type of operation
26
s.Io
R/W
Control input/outputs from serial
0 ... 1023
0
InNTC
-
Led 2 Led 1 Out rL Out SCR In Dig inTV
inCT
PV
Bit
9 8 7 6 5 4 3 2 1 0
Table of virtual register addresses
Parameter
bit
Resource enabled
Address of
image register
Format
Name of register
S. lo
0
Input PV
132
Word
SERIAL_PV
1
Input In.TA
133
Word
SERIAL_INTA
2
Input In.TV
134
Word
SERIAL_INTV
3
Input Digital
131
Word bit 2
SERIAL_IO
4
Output Out SSR
131
Word bit 0
SERIAL_IO
5
Output Out rL
131
Word bit 1
SERIAL_IO
6
Led 1
131
Word bit 3
SERIAL_IO
7
Led2
131
Word bit 4
SERIAL_IO
9
Output In.NTC
135
Word
SERIAL_INNTC
Virtual instrument control is activated by means of parameter hd.1.
By setting parameter S.Io you can enable the writing of some parameters via serial line, set the value of
inputs and the state of outputs.
Enabling the PV input means being able to exclude the local Tc or RTD acquisition and replace it with the value written
in the register SERIAL_PV.
Содержание GTF
Страница 2: ...2 80961F_MSW_GTF GTF Xtra_07 2018_ENG ...