6. POWER SUPPLY, GROUNDING AND SHIELDING

The power supply terminal block is shown in the figure below.

Figure 6.1

3 conductor 1,5mmq wire size minimum, minimum temperature conductor rating 105°C.

Note:  Ensure that the power supply has enough power 

capacity for the operation of the equipment.

The unit must always be grounded to earth with 1,5mmq wire 

size minimum. Grounding helps limit the effects of noise due 

to electromagnetic interference on the control system.

Earth connection will have to be done using either the 

screw or the faston terminal located near the power supply 

terminal block. A label helps identify the ground connection. 

Also connect to ground the terminal 3 on the power supply 

terminal block.

The power supply circuit may be floating or grounded. In the 

latter case, connect to ground the power source common as 

shown in figure (see below) with a dashed line. When using 

the floating power scheme, note that the panes internally 

connects the power common to ground with a 1MΩ resistor 

in parallel with a 4,7nF capacitor.

The power supply must have double or reinforced insulation.

The suggested wiring for the power supply is shown below..

Figure 6.2

All the electronic devices in the control system must be properly grounded. Grounding must be performed according to 

applicable regulations.

Содержание G-Vision 66-070

Страница 1: ...ree download from the GEFRAN website www gefran com Installers and or maintenance personnel are required to read this manual and to precisely follow the instructions contained in it and in its attachm...

Страница 2: ...notice The information contained in this document is provided for informational purposes only While efforts were made to verify the accuracy of the information contained in this documentation it is pr...

Страница 3: ...Environment 11 4 3 Safety instruction 11 4 4 Installation Procedure 11 5 CONNECTIONS 12 5 1 Serial Port 12 5 2 Ethernet Port 13 5 3 Optional plugin module 13 5 4 Optional plugin module installation pr...

Страница 4: ...les and such failure may cause death or serious injuries SAFETY GUIDE ATTENTION indicates a failure to observe safety rules and that deficiency may cause damage CAUTION indicates a failure to observe...

Страница 5: ...are for powerful HMI applications Gateway function with OPC UA Server and Client Secure connectivity with Gefran Cloud and full network separation Powerful browser wih industry standard Web engines 2...

Страница 6: ...5 54 00 00 POWER SUPPLY 24V 0 70A CODE F086941 120408A04002000 AA00011FT000000561AA Gefran Soluzioni srl Via Sebina 74 1816 This product contains a battery Dispose of the battery according to local re...

Страница 7: ...22 CISPR 16 2 3 Electrostatic discharge immunity test 8 kV air electrostatic discharge 4 kV contact electrostatic discharge EN 61000 4 2 Radiated radio frequency electromagnetic field immunity test 8...

Страница 8: ...istance of the front glass for an exposure time of 24 hours without visible changes Betadine 10 Povidone Solution Cola Electrode Gel Paste Hydrogen Peroxide 3 Solution NaCl 0 9 Solution Coffee Dextros...

Страница 9: ...odules Ratings Power supply 24 Vdc 10 to 32 Vdc Current Consumption 0 7 A at 24 Vdc max 1 0 A at 24 Vdc max 1 2 A at 24 Vdc max 1 7 A at 24 Vdc max Battery Rechargeable Lithium battery not user replac...

Страница 10: ...mm 5 79 176mm 6 90 136mm 5 35 47mm 1 85 8mm 0 31 G Vision 66 101 282mm 11 10 197mm 7 80 271mm 10 67 186mm 7 32 56mm 2 20 8mm 0 31 G Vision 66 156 422mm 16 60 267mm 10 50 411mm 16 18 256mm 10 00 56mm 2...

Страница 11: ...he cutout must be flat screw up each fixing screw until the bezel corner get in contact with the panel the cutout for the panel must be of the dimensions indicated in this manual The IP66 is guarantee...

Страница 12: ...e PLC or with another type of controller Different electrical standards are available for the signals in the PLC port connector RS 232 RS 422 RS 485 The serial port is software programmable Make sure...

Страница 13: ...ivity BLINKING Activity 5 3 Optional plugin module G Vision panels have several optional plugin module multiple modules configurations are possible Slot 2 and Slot 4 are available only if plugin modul...

Страница 14: ...S 4G wireless modem 1 Y Max modules refers to max number of modules can be plugged into the HMI all slots If you are planning to use GV_PLUG 232 and GV_PLUG 485 additional serial ports you will obtain...

Страница 15: ...ston terminal located near the power supply terminal block A label helps identify the ground connection Also connect to ground the terminal 3 on the power supply terminal block The power supply circui...

Страница 16: ...d not be used for purposes and methods other than indicated in this document and in the documentation accompanying the product 9 GETTING STARTED G Vision devices products delivery configuration is bas...

Страница 17: ...grade and recovery not available when running in User Mode Activation of System Settings in User Mode Factory default status Press System Setting button on the HMI screen GF Designer HD runtime runnin...

Страница 18: ...e System on time backlight on time Logs Enable persistent log for BSP and allows exporting it Date Time Network Change the device date and time including time zone and NTP Server Configure IP Address...

Страница 19: ...81085_G Vision 66_12 2021_ENG 11 UNPACKING AND PACKING INSTRUCTIONS Figure 11 1 G Vision 070 G Vision 101 Figure 11 2 G Vision 156 G Vision 215 To repack the unit please follow the instructions backwa...

Страница 20: ...Gefran Soluzioni srl Via Sebina 74 25050 Provaglio d Iseo BS Italy Tel 39 0309888 1 Fax 39 0309839063 info gefran com http www gefran com www gefran com en gefran soluzioni...

Отзывы: