![gefran CAN-IO Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/gefran/can-io/can-io_installation-and-user-manual_2205693013.webp)
13
80990B_MHW_CAN-IO_12-2016_ENG
ANALOGUE OUTPUT
VOLTAGE ±10 V
Max number
8 (orderable in groups: 2, 4, 6, 8)
Type
Single ended voltage ±10 V
Max output current
20 mA
Refreshing time
10 ms
Settling time
(“settling time”)
1 ms
Output format
Type: INT
Resolution: 13 bit (-4096 … 4095)
LSB: 2,44 mV
Max error @ 25 °C
±0,5% scale bottom
Protections
Short circuit ±10V: yes
Overpressure: max 1 kV per 1 ms
Electric insulation
Channel-channel: no
Channel-bus: 2 kV
ANALOGUE OUTPUT
CURRENT 0/4 ��� 20 mA
Max number
8 (orderable in groups: 2, 4, 6, 8)
Type
Current, 0 ... 20 mA
Max voltage
12 V
Max charge
600 Ω
Refreshing time
5 ms
Settling time
(“setting time”)
1 ms
Output format
Type: UINT
Resolution: 12 bit (0 … 20 mA: 0 … 16384
4 … 20 mA: 3277 … 16384)
LSB: 1,22 μA
Max error @ 25 °C
±0,8% scale bottom
Protections
Overvoltage: max 1 kV per 1 ms
Electric insulation
Channel-channel: no
Channel-bus: 2 kV
ENVIRONMENTAL
CONDITIONS
Operating temperature
0 ... +50 °C (according to IEC 68-2-14)
Storage temperature
-20 ... +70 °C (according to IEC 68-2-14)
Relative humidity
5 ... 95% RH non-condensing (in according to IEC 68-2-3)
ASSEMBLY
Direct on plate, with spacers
On 35 mm DIN bar, horizontal or vertical (optional)
DEGREE OF
PROTECTION
IP 20 (optional)
WEIGHT
Depending on the I/O configuration
For assembly on plate: 0.6 kg max
For assembly on DIN runner: 0,85 kg max
CERTIFICATION
CE
UL by specific request
CE STANDARDS
EMC conformity
(electromagnetic compatibility)
Observance of Directive 2014/30/EU
EN61131-2: Programmable Controllers
Part 2: Equipment requirements and test.
LV conformity
(low voltage)