3.1
P
ower
connections
RECOMMENDED WIRE GAUGES
3 • ELECTRICAL CONNECTIONS
Table 4
GTF CURRENT LEVEL
TERMINAL
CABLE WIRE
WIRE TERMINAL
TIGHTENING TORQUE /
TOOL
25A
1/L1, 2/T1, PE
4 mm²
10 AWG
Wire terminal / Eye
D. 6mm
2.5 Nm / Phillips screwdriver
PH2 - PH3
40A
1/L1, 2/T1, PE
10 mm²
7 AWG
Wire terminal / Eye
D. 6mm
2.5 Nm / Phillips screwdriver
PH2 - PH3
50A
1/L1, 2/T1, PE
10 mm²
7 AWG
Wire terminal / Eye
D. 6mm
2.5 Nm / Phillips screwdriver
PH2 - PH3
60A
1/L1, 2/T1, PE
16 mm²
5 AWG
Wire terminal / Eye
D. 6mm
2.5 Nm / Phillips screwdriver
PH2 - PH3
-
3/L2 (Ref. Vline)
0.25 ...2.5 mm²
23...14 AWG
wire terminal tip
0.5 ...0.6 Nm / Screwdriver blade
0.6 x 3.5 mm
Note: Cables must be copper “Stranded Wire” or “Compact-Stranded Wire” type with maximum operating temperature 60/75°C