7 • SOFTWARE CONFIGURATION

- Normal frequency value

- Maximum peak value of frequency

- Minimum peak value of frequency

+4 - with settable sampling time

+8 - with fixed scale

In3/ input 3 function (for timer and counter)

0 - hold - freezes display

1 - up/down for count

out/ output function (see Description of output functions):

- U1 Standard

- U2 Monostable cyclical

- U3 Cyclical with timed Reset

- U4 Latch1 on output

- U5 Latch2 on output

- U6 Monostable non-cyclical

- U7 Double cyclical counter with overlapped counts

- U8 Double cyclical counter with alternating counts

(Note: U7 and U8 for Typ = 1 only)

LoG/ Logic of digital inputs

 

LoG 

IN.2 

 

IN.3

 

  0 

Active when closed  Active when closed

 

  1 

Active when open 

Active when closed

 

  2 

Active when closed  Active when open

 

  3 

Active when open 

Active when open

Note: state of first input IN1 is defined by jumper (see HW Config.).

Sc.1/ Select Time 1 scale (for timer only) seconds (0.000-9.999)

0 - seconds (00.00-99.99)

1 - seconds (000.0-999.9)

2 - seconds (0000-9999)

3 - minutes/seconds (0.00-99.59)

4 - hours/minutes (0.00-99.59)

Sc.2/ Select Time 2 scale (for timer and counter)

0 - seconds (0.000-9.999)

1 - seconds (00.00-99.99)

2 - seconds (000.0-999.9)

3 - seconds (0000-9999)

4 - minutes/seconds (0.00-99.59)

5 - hours/minutes (0.00-99.59)

Ps./Select counter prescaler

0 - count : 1

1 - count : 2

2 - count : 10

3 - count : 100

4 - count x 2

Mul./Multiplier (for counter or frequency meter) 1-100

div./Divisor (for counter or frequency meter) 1-100

(see “Operation of Counter and Frequency meter”)

P.d./Decimal point position (counter and frequency meter)

0 - without decimal figures

1 - 1 decimal figure

2 - 2 decimal figures

3 - 3 decimal figures

t.SP/Frequency meter sampling time 0.0-10.0 seconds.

8 • DESCRIPTION OF OUTPUT FUNCTIONS

The figures show the Timer functions (Typ=0) with countdown (Fun=0). For counters 

(Typ=1) in cases out=1...6, “Timer” and “Timer 1” become “Counter 1” and “Counter 

2”. For the frequency meter (Typ=2) with out=4, there is a second setpoint for 

hysteresis.

a) IN3 = 0: IN 3 with HOLD display function;

b) IN3 = 1: IN3 with UP/DOWN function

out=1 Standard U1 Function

Timing begins and proceeds until the trip point if the IN1 signal is present. The output 

energizes when the set time has elapsed.

When the IN2 signal arrives, the output resets and the timer returns to its preset value.

The timer restarts when the IN1 signal is received. 

In case AIN3 does not cause changes in operation of inputs and outputs, but simply 

freezes the displayed value.

In case B, if IN3 arrives when the timer count has already started but not yet finished, 

it causes the count to reverse direction (up instead of down).

In this condition, the current timer value continues to increase until reaching the full 

scale of the time base.

When IN3 is removed, the countdown resumes from the value reached and goes 

toward the trip point.

out=2 Cyclical monostable U2 Function

If input IN1 is present, when the timer reaches the trip point it immediately reloads the 

preset value and begins a new countdown (cyclical function).

The output energizes each time the setpoint is reached and stays energized for time 

S.P.2.

The arrival of input IN2 resets the output and the two timers (S.P.1 and S P.2) return 

to their preset values.

In case B, input IN3 reverses the count of timer 1 (S.P.1) only; therefore, timer 2 (if 

started) always reaches end of time state regardless of the presence of IN3

Function (U1) non-cyclical single timer with reset 

(Standard)

Timer

IN1

IN2

Relay

IN3

Timer

Relay

(b)

(a)

Time

Function (U2) Cyclical monostable timer with reset

Timer 1

IN1
IN2

Relay

IN3

Relay

Timer 2

Timer 1
Timer 2

(b)

(a)

Time

5

80469C_MHW_556_02-2011_ENG

Содержание 556

Страница 1: ...in peak functions IN3 Hold input In this configuration as well the display and setting can be expressed as the value converted into engineering units by means of the MOL and DIV factors DRM Gefran instruments replaced by model described Output functions The output performs the following functions configuration as timer with countdown and input IN3 with HOLD a or UP DOWN b function In all other cas...

Страница 2: ...eters can be set during configuration The decimal point on the right indicates display of set 2 F LED signals I1 State of IN1 input signal Start Stop in case of timer Clock in case of counter and frequency meter I2 State of IN2 input signal in case of timer and frequency meter IN3 in case of counter LED off corresponds to input OFF LED on corresponds to input ON O State of output relay LED on rela...

Страница 3: ...N2 RESET IN3 HOLD or UP DOWN see configuration of IN3 functions If the function of IN3 is defined as UP DOWN it causes inversion of the current value of Time 1 Time 2 maintains its direction If the timer is configured to down Fun 0 it loads the preset value and counts down toward zero by closing IN3 if configured to active when closed you tempo rarily reverse the direction of time 1 to up until Fu...

Страница 4: ...ions displayed value frequency MUL DIV Example 1 You want to display the number of rpms of a wheel with 250 pulses rev Rpm frequency 60 250 frequency 6 25 Set FP 0 MUL 6 DIV 25 Example 2 You want to determine the frequency in impulses second of a system with a decimal figure using a sampling time of 5 sec for greater stability Set FP 12 MUL 1 DIV 5 P d 1 t SP 5 0 In operation as frequency meter th...

Страница 5: ... FUNCTIONS The figures show the Timer functions Typ 0 with countdown Fun 0 For counters Typ 1 in cases out 1 6 Timer and Timer 1 become Counter 1 and Counter 2 For the frequency meter Typ 2 with out 4 there is a second setpoint for hysteresis a IN3 0 IN 3 with HOLD display function b IN3 1 IN3 with UP DOWN function out 1 Standard U1 Function Timing begins and proceeds until the trip point if the I...

Страница 6: ...scribed for function U4 with the difference that the relay remains energized even if the timer value exceeds the trip point out 6 Function U6 Non cyclical monostable with reset Similar to function U3 but with the difference that at the end of timings the timer reloads the preset value only after input IN2 out 7 Function U7 Cyclical double counter with superimposed counts Similar to U2 but instead ...

Страница 7: ...If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least in pairs Power supplied from a disconnecting switch with fuse for the device section path of wires from switch to devices should be as straight as possible the same supply should not be used to power relays contactors solenoid valves etc if the voltage waveform...

Отзывы: