Setting

 

Symbol

 

Description

 

Range

 

Regulacja obrotów 
pompy kolektorów 
(Collector pump 
rotation speed 
adjustment)

 

RegFaz

 

Main pump (collector pump) adjustment. If the 
collector pump adjustment is selected in the Controller 
settings, the Controller will adjust the collector pump 
rotation speed. If the collector pump speed adjustment 
option is disabled, the Controller will only control the 
pump in the on/off operation mode.

 

In schemes 6, 10, 12, 14, 15 and 16 the collector pump 
rotation speed adjustment is never active.

 

No / Yes

 

Tryb pracy pompy 
cyrkulacyjnej 
(Circulation pump 
operation mode)

 

 

When it is set to “Ci

ą

gły” (Continuous), the 

circulation pump is activated in the hours set in the 
“Program czasowy” (Time Programme) menu. If it is 
set to “Przerywana” (Intermittent), the circulation 
pump will additionally operate in the hours set in the 
“Program czasowy” (Time Programme) menu, 
however, it will operate on a cyclical basis, activating 
for 10 minutes, then after 10 minutes deactivating for 
another 10 minutes after it will again activate for 10 
minutes.

 

Interm. / 
Contin.

 

Moc kolekt. wył

ą

cz. 

kotła, grzałki, 
pompy ciepła 
(Collector power for 
deactivated boiler, 
heater, heat pump)

 

 

Setting applied in schemes 3, 4, 5 and 14. The 
Controller calculates the collector power and 
deactivates the boiler or the heater if the calculated 
power exceeds the power defined in the control 
setting. When the collector power value is lower than 
the value defined in the settings, the boiler, heater and 
pump outputs are controlled in accordance with their 
control algorithm.

 

100…3000W

 

Ochrona przed 
przegrzaniem 
kolektorów 
(Collector 
overheating 
prevention)

 

ZabPrzeg

 

Setting defines enabling or disabling the boiler 
overheating prevention function.

 

No / Yes

 

Max. temp. T2 
wył

ą

cz. ochrony 

przegrz. kolektorów 
(Max. T2 
temperature for 
deactivating 
collector 
overheating 
prevention)

 

T

maxprzeg

 

Setting defines the maximum temperature within the 
tank when the collector overheating function is 
enabled. This setting has priority over the 
T2

max

.setting.

 

60…85ºC

 

Ochrona przed 
zamro

ż

eniem 

kolektorów 
(Collector freezing 
prevention)

 

Przeciw.Zam

 

Setting enables/disables the collector freezing 
prevention function.

 

No / Yes

 

Wybór priorytetu 
grzania (Heating 
priority selection)

 

PriorytAB

 

Setting associated with schemes 9, 10, 11, 12 and 16. 
Defines the priority of the tank / pool heating.

 

A / B

 

Ochrona przed 
bakteriami 
Legionella 
(Protection from 
Legionella)

 

 

Setting associated with schemes 3, 4, and 14. Defines 
whether the anti-legionella function is enabled or 
disabled.

 

No / Yes

 

Содержание GH20SB

Страница 1: ...sp ka z o o 32 060 Liszki Cholerzyn 376 tel 012 6369811 6361290 fax 012 6362002 ____________________________________________________ USER MANUAL FOR SOLAR COLLECTOR SYSTEM CONTROLLER GH20SB Software...

Страница 2: ...heater 28 6 5 Scheme 5 the basic scheme with a circulation pump and a heat pump 29 6 6 Scheme 6 the basic scheme with a circulation pump activating domestic hot water heating after the boiler achieve...

Страница 3: ...of pumps cooperating with collector batteries placed in various directions additionally the system controls a circulation pump 34 6 16 Scheme 16 a system allowing control of pumps cooperating with co...

Страница 4: ...igurations System scheme display Device operation animation in the system scheme Collector pump rotation speed adjustment External device manual control option Calculation of collector instantaneous p...

Страница 5: ...in pump output Maximum current rating 3 15A O2 Relay output dry switch relay Maximum current rating 8A S1 S2 NC normally closed S2 S3 NO normally open O3 Relay output live 230VAC Maximum current ratin...

Страница 6: ...roller from the power supply for a moment 3 2 Standby Mode In this mode the LCD display is slightly backlit and the Controller name and the current software release are shown on the screen In the stan...

Страница 7: ...power is displayed as calculated by the Controller When the collector pump is deactivated or the sensor on the collector return as a rule it is sensor T3 is disconnected the power indication is replac...

Страница 8: ...return to the main menu screen Press to cancel changes and return to the main menu screen Press to cancel changes and cause the Controller to switch to the standby mode 3 3 4 Settings Configuration Me...

Страница 9: ...tion of the following settings Solar collector type Flat Tube T1 T2 temperatures difference for deactivating collector pump 2 15 C Temperatures difference for activating additional pump valve 2 15 C M...

Страница 10: ...nday The horizontal arrow shown above the scale at the top of the screen indicates the hour range active for edition The edition of the time programme begins with defining the device operation on week...

Страница 11: ...ngs configuration menu screen When you go to this screen the setting value flashes Press and to define a new heating medium freezing point temperature in the range from 35 to 0 C Press to save the new...

Страница 12: ...hes Use and to set a new value Press to save the new value and exit the setting edition option Press to cancel the change and exit the setting edition option Press when setting edition is not active t...

Страница 13: ...rences for activating additional pump valve 5 C 5 C 5 C 5 C 5 C 5 C 5 C 5 C 5 C Max temp T2 wy czenia pompy kolektor w Max T2 temperature for deactivating collector pump 65 C 65 C 65 C 65 C 65 C 65 C...

Страница 14: ...Nie No Nie No Nie No Nie No Nie No Nie No Nie No Max temp T2 wy ochrony przegrz kolektor w Max T2 temperature for deactivating collector overheating prevention 80 C 80 C 80 C 80 C 80 C 80 C 80 C 80 C...

Страница 15: ...play settings edition option Choose sound edition option Choose language selection option Press and to switch between options To confirm the selection of an option press Press to return to the main me...

Страница 16: ...on the main menu screen and then Display on the Controller configuration menu screen On this screen you can edit Display backlight intensity 1 10 Inactivity time after which the backlight will be auto...

Страница 17: ...d setting During active edition the setting value flashes Use and to set a new value Press to save the new value and exit the setting edition option Press to cancel the change and exit the setting edi...

Страница 18: ...switching to manual operation the control algorithm is wholly suspended and the user has full control over the status of the outputs external devices Depending on the selected system configuration the...

Страница 19: ...value and exit the setting edition option Press to cancel the change and exit the setting edition option Press when setting edition is not active to return to the main menu screen Press to cause the...

Страница 20: ...anuary to December When the graphical presentation in the form of bar charts is displayed in the left upper corner of the screen the highest value in the given interval appears to which the height of...

Страница 21: ...you can change the status of the holiday function and define holiday start and end date Press and to switch between settings and press to edit the currently highlighted setting During holiday start o...

Страница 22: ...value and press to save the new value and exit the holiday function status edition Press to cancel the change and exit the holiday status edition option Press when setting edition is not active to re...

Страница 23: ...e The setting is applied to controlling more extensive systems 2 15 C Max temp T2 wy czenia pompy kolektor w Max T2 temperature for deactivating collector pump T2max Setting associated with temperatur...

Страница 24: ...eater heat pump Setting applied in schemes 3 4 5 and 14 The Controller calculates the collector power and deactivates the boiler or the heater if the calculated power exceeds the power defined in the...

Страница 25: ...Description Range Poziom jasno ci wy wietlacza Display backlight intensity Setting defines display backlight intensity 1 10 Czas wygaszenia wy wietlacza Display sleep time Setting defines time withou...

Страница 26: ...ated in a week in the night from Sunday to Monday The anti legionella function does not work during holidays 5 3 Holiday Function The holiday function consists in totally disabling the control of the...

Страница 27: ...r Required T2 Tank sensor Required T3 Sensor for calculating power energy Optional T4 Tank sensor Optional 6 2 Scheme 2 the basic scheme with a circulation pump Output Device connected O1 Collector pu...

Страница 28: ...ensor Required T2 Tank sensor Required T3 Sensor for calculating power energy Optional T4 Tank sensor Required 6 4 Scheme 4 the basic scheme with a circulation pump and an electric heater Output Devic...

Страница 29: ...red T3 Sensor for calculating power energy Optional T4 Tank sensor Required 6 6 Scheme 6 the basic scheme with a circulation pump activating domestic hot water heating after the boiler achieves the re...

Страница 30: ...equired T2 Tank sensor Required T3 Sensor for calculating power energy Optional T4 Tank sensor Required 6 8 Scheme 8 a system of two heaters allows additional heating of the circulation return with so...

Страница 31: ...r Required T2 Tank sensor Required T3 Sensor for calculating power energy Optional T4 Pool sensor Required 6 10 Scheme 10 a system with two collector pumps for domestic hot water heating and pool wate...

Страница 32: ...or Required T2 Tank sensor Required T3 Sensor for calculating power energy Optional T4 Tank sensor Required 6 12 Scheme 12 a system with two collector pumps for domestic hot water heating in two solar...

Страница 33: ...calculating power energy Optional T4 SH return sensor Required 6 14 Scheme 14 a domestic hot water heating system with solar collectors Additionally the system controls a gas boiler and activates dom...

Страница 34: ...cription T1 Collector sensor Required T2 Tank sensor Required T3 Collector sensor Required T4 Tank sensor Required 6 16 Scheme 16 a system allowing control of pumps cooperating with collector batterie...

Страница 35: ...dicated by audio signal In the alarm mode you can browse the menu system configure settings and manually control the external devices The information which sensor is in alarm condition is available in...

Страница 36: ...P P U H Geco Sp ka z o o 32 060 Liszki Cholerzyn 376 tel 48 12 6369811 48 12 6361290 fax 48 12 6362002 http www geco pl...

Отзывы: