GERC_RLY  Rev 2 Wiring and Usage manual 

January 9, 2007 

4

Consult the documentation for the controller software to determine which pin the software 
expects for an EStop signal. 
 

For correct operation, the EStop pin on the PC parallel port must be actively pulled high 
via a resistor.  The GERC_RLY does not “make it go high”.   
 

Thankfully, the input electronics of most parallel ports already do this.   
 
Finally, don’t forget to configure the software in the PC for an active high EStop signal.   

 
J3 - Error/Reset connections 

 

This is how the GERC_RLY communicates with the Geckos. 
 
Using figure 1 (below) as a guide, connect a wire from the X Y Z and A points of J3 to Pin 5 of 
the relevant Gecko.  (Four Geckos, four wires) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note: These inputs are a direct, unprotected connection to the microcontroller.  Do not 
connect these inputs to anything except the Error/Reset pin of a Gecko G3x0.

 

 
J4 - EStop Switch  

 

The EStop switch input is a designed to be connected to an external “Big Red Switch”, located 
in such a position that it is easy for the operator to activate it should the need arise.   
 
This switch must be 

closed

 for the GERC_RLY to operate.  When the switch contacts 

open

the GERC_RLY will stop motor activity (by first placing the Geckos into reset and then 
removing power to the Geckos).   
 

X axis motor 

J3 

X axis Gecko 

GERC 

Pin 5 

Figure 1 

Содержание G3 0 Series

Страница 1: ...Gecko G3x0 Error Reset Controller Relays included version Rev 2...

Страница 2: ...gic and only partly electronics I decided to use a microcontroller My design goals were these Automatically provide the 5 second reset required at powerup I don t think in this day and age of electron...

Страница 3: ...ervo electronics fail in such a manner simply saying to the Gecko via pin5 please stop will not work causing extreme badness However for those people who for whatever reason choose not to add relays t...

Страница 4: ...e total consumption exceed 200 ma J2 EStop output The EStop output allows the GERC_RLY to alert the controller typically a PC or an intelligent break out board that something bad has happened Technica...

Страница 5: ...Geckos Using figure 1 below as a guide connect a wire from the X Y Z and A points of J3 to Pin 5 of the relevant Gecko Four Geckos four wires Note These inputs are a direct unprotected connection to...

Страница 6: ...r will be ineffective The EStop switch carries relay power and as such the contacts cannot be shared with any other device If an EStop switch is to be used to turn off the lathe or mill motor for exam...

Страница 7: ...is must be supplied through a power switch and fuse in accordance with local regulations It is the outer two connections that are used the inner terminal is used for isolation only A suitable value fo...

Страница 8: ...a power resistor connected across the motor terminals This connection is actually through the Gecko not directly to the motor but the nature of the Gecko output stage is such that this is the correct...

Страница 9: ...e LED for that axis is ON steady With all axes enabled all LEDs are on steady With all axes disabled no LEDs are on Normal operation then is all LEDs on Reset Any time the unit is reset the LED for an...

Страница 10: ...k in sequence X LED then Y LED then Z LED then A LED then X LED again Note Once the EStop condition is cleared the GERC_RLY requires a reset either by toggling the AllStop Reset switch or by a power c...

Страница 11: ......

Страница 12: ...in Zin Ain R6 R9 1 2 3 4 J3 IN1 1 IN2 2 IN3 3 IN4 4 IN5 5 IN6 6 IN7 7 IN8 8 VS 9 OUT1 18 OUT2 17 OUT3 16 OUT4 15 OUT5 14 OUT6 13 OUT7 12 OUT8 11 COM CATH 10 U3 ULN 2803A Xout YOut Zout Aout VEStop Xer...

Страница 13: ...2 are ELECTRONICS S1 SW SPDT Front Panel PCB D1 LED LED D2 LED LED 1 2 3 4 5 6 7 14 13 12 11 10 9 8 J12 S2 SW SPDT S3 SW SPDT S4 SW SPDT LED LED S1 S2 S3 S4 S5 1 2 3 4 5 6 7 14 13 12 11 10 9 8 J11 XLE...

Страница 14: ...ELECTRONICS R10 4r7 VRelay ES_In A_In VRelay K1 P B T90 D5 50sq100 0 To Motor To Power 1 2 3 J9 0 To Motor To Power 1 2 3 J8 VRelay K2 P B T90 R11 4r7 Z_In R12 4r7 D6 50sq100 0 To Motor To Power 1 2...

Страница 15: ...ocument Number REV B GERC_RLY 2 Title GERC with relays power supply are ELECTRONICS Heatsink VEStop 1 2 3 J5 6 4 3 1 7 9 10 12 T1 MICROTRAN D9 1n5820 D10 1n5820 C7 220u C10 220u C8 220u IN 1 OUT 3 G N...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Отзывы: