OPERATION WITH NORMALLY
CLOSED (N.C.) VALVE
OPERATION TEST
Before carrying out the operation test, open the cover under the
three LED lights (Fig. 10) with a flat-headed screwdriver.
Fig.10
When this is done, it is possible to test operation of the instrument
by pressing and holding the little button on the
Sensor module
(Fig. 11) for at least 2 seconds; all the LEDs turn on and the buzzer
and relay output are activated for 5 seconds.
Fig.11
You will then need to re-engage the electric valve connected to the
output of the gas detector (if present).
Fig.9
ROUTINE TESTING
You are advised to ask the installer to give the detector a general
test at least once a year.
IMPORTANT: Do not use pure gas, such as that in a lighter,
directly on the sensor since the sensor could be irremediably
damaged.
ELECTRICAL CONNECTION WITH SEVERAL
DETECTORS:
Connection of two detectors with a single electric valve (Fig. 8-9)
is shown in the diagrams below. It is possible to connect more
than two detectors, repeating the same connections.
OPERATION WITH NORMALLY
OPEN (N.O.) VALVE
Fig. 6 Example of jumper with N.C. contact (
CONSTANT OUTPUT
)
and
Normally Open electric valve
with load at 230Vac.
JUMPER WITH N.C.
(CONSTANT OUTPUT)
Fig.7 Esempio jumper su N.C. (
USCITA COSTANTE
) ed elettrovalvola
Normalmente Chiusa
con carico a 230Vac.
Aspiratore, Ventilatore, Sirene...etc. .a 230Vac
Fig.8
N.O. MANUAL RESET VALVE
Fig.6
Extractor, Fan, Buzzer, etc. at 230Vac
N.C. MANUAL RESET VALVE
TO BE COMPILED BY THE INSTALLER:
Date of installation ________________________________________
Date of replacement ______________________________________
Attention: the detector must be replaced 15 years after the
date of installation on this voucher
Site of installation _________________________________________
Serial number (s.n.) _______________________________________
(Written on the inside of the plastic container).
Date of initial replacement of sensor module:____________________
Date of second replacement of sensor module:__________________
Attention: the entire detector must be replaced five years
after second replacement of the sensor module.
Stamp
Signed ________________
N.C. MANUAL RESET VALVE
N.O. MANUAL RESET VALVE