Operation

Actuating the flush

The electronic flush actuation takes place by means of infrared user detection. The user 
detection range starts approx. 50 cm in front of the sensor window.
After a minimum detection time of 7 seconds, a flush is actuated when the user leaves the 
detection range.

Rectifying malfunctions

Malfunction

Cause

Rectification

No flush actuation

Water supply valve is closed

`

Open the water supply 
valve

No pressure in water net

`

Test the water pressure

No mains voltage, green LED on 
power supply unit does not light 
up (mains-operated flush 
controls)

`

Test power supply (fuse 
in electrical distributor)

Battery voltage low (battery-
operated flush controls)

`

Replace the batteries, 
see "Maintenance"

Sensor window is dirty

`

Clean sensor window

Sensor window is scratched

`

Contact a skilled person

Unknown error

`

Contact a skilled person

Flush runs continuously

Sensor electronics are defective

`

Contact a skilled person

Solenoid valve is defective

`

Contact a skilled person

Flush actuates 
unintentionally

Sensor window is dirty

`

Clean sensor window

Sensor window is scratched

`

Contact a skilled person

Sensor windows are affected by 
influences in the room (mirrors, 
metal surfaces, etc. on the wall 
opposite)

`

Contact a skilled person

Urinal ceramic is not being 
flushed out sufficiently

Flush time set incorrectly

`

Increase flush time, see 
"Maintenance"

Throttle is not open sufficiently

`

Contact a skilled person

Flush water is splashing out 
from the urinal ceramic

Excessive flow rate

`

Contact a skilled person