GENERAL INFO
Main setup data
Descriptio
Grasso V 700HS .. V 1800HS
Remark
General Limits of
Operation
Caution!
Start frequency
max. 6 starts per hour
The
NO-solenoid has to
be de-energised 20
seconds after starting
the compressor
motor
to enabel the motor to
reach the minimum
speed and the
compressor to develop
the required oil pressure
Time interval between
stopping and re-starting
min. 2 minutes
Time interval between
starting and re-starting
min. 10 minutes
Time interval between
loading and unloading
min. 3 minutes
For continuous minimum
part-load (i.e. more than
30 minutes) consult
Grasso.
Adjust the steps between
up and down loading, in
such a way that the
system is running stable.
Oil level
25-75% crankcase sight glass
Control oil pressure
suction pr 8 bar (g)
Lubricating oil pressure
difference
between 1.3 and 4.5 bar Setting approx. 2.0 bar (g)
After a mimimum of 15
minutes running time at
an oil temperature of
approx. 50
o
C
Max. discharge
temperature
170 °C
Min. suction pressure
0.3 bar(a)
Max. intermediate
pressure
Max. suction pressure
7 bar (a)
P
discharge
- P
suction
≤ 19.0 bar (g)
Superheat
>0 K
Oil discharge -
running
in - filter
Factory mounted;
to be replaced after max. 100 running hours
by “normal” oil
discharge filter element
Oil discharge filter
Supplied loose; replacement for factory mounted running in filter
P-NL-094_imm_VHS_English_13
26.07.2021
9