General limits and fields of operation
REFRIGERANT
NH
3
Design pressure
PS
s
*
19
Grasso V(T)
-
26.5 bar(a)
This pressure deviates from the so
called max. discharge
pressure=condensing pressure
(allowed during operation) as stated
in the table.
Discharge temperature
t
e
Grasso V
max.
+170 °C
This is the actual discharge
temperature, measured directly in
the gas flow just before the
discharge connection. The given
value also applies to the LP stage
of two-stage compressors.
Discharge temperature LP
Grasso VT
Pressure ratio per stage (p
c
/p
o
or p
c
/p
m
or p
m
/p
o
)
Pressure ratio limits are not
absolute but arbitrary values
based on practical
considerations
j
-
min.
1.5
max.
10
Pressure difference
delta-p
Grasso V
300(T) .. 600(T)
max.
(p
c
- p
o
) <= 25.5 bar
The standard built-in overflow
safety valve(s)
(p
c
- p
ambient
) <= 25.5 bar
Grasso V
700(T) ..
1800(T)
max.
(p
c
- p
o
) <= 19.0 bar
The standard built-in overflow
safety valve(s)
(p
c
- p
ambient
) <= 25.5 bar
Oil temperature in crankcase
t
oil
°C
min.
>10
o
C and > T
saturated crankcase
pressure at stand still
+ 15 K
Indicated minimum value is the
lowest oil temperature at which the
compressor is allowed to be started.
max.
< 70
o
C, depending on type of oil
The maximum oil temperature
depends on the operating
conditions of the compressor and
the oil type used.
A minimum actual oil viscosity of 10
cSt in the bearings is always
required.
4.3
STARTING UP OF TWO-STAGE COMPRESSORS
Procedure for starting from compressor standstill
In the case of two-stage compressors it is very important that immediately after
the period of automatic fully unloaded start (ensured by the corresponding three-
way solenoid valve in the control pressure supply line from the oil pump; only one
or more H.P. cylinders become operative, viz. only those cylinders of which the
suction valve lifting mechanism is directly and permanently connected to the
19
“PSs“ is mentioned on type plate of the compressor (Possibly "Pd" is mentioned for compressors
delivered before 1-Mar-2013)
APPENDIX; Product Information (PI)
STARTING UP OF TWO-STAGE COMPRESSORS
0089288gbr_11
52
30.10.2017
Содержание Grasso V Series
Страница 6: ...0089288gbr_11 6 30 10 2017 ...
Страница 8: ...0089288gbr_11 8 30 10 2017 ...
Страница 10: ...0089288gbr_11 10 30 10 2017 ...
Страница 61: ...Fig 16 Grasso V 6 Pre lubrication valve APPENDIX Product Information PI 0089288gbr_11 30 10 2017 61 ...