![GEA Bock HG8 Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/gea/bock-hg8-series/bock-hg8-series_assembly-instructions-manual_572180028.webp)
28
D
GB
F
E
I
Ru
09790-02.2018-DGbFEIRu
7.2 Work to be carried out
7
|
Maintenance
In order to guarantee optimum operational reliability and service life of the compressor,
we
recommend
carrying out servicing and inspection work at regular intervals:
Oil change:
-
not mandatory for factory-produced series systems.
-
for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.
Annual checks:
Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.
HG8 / ...
2470-4 (S)
2830-4 (S)
3220-4 (S)
Designation
Item No.
Item No.
Item No.
Set of gaskets kit
80235
Valve plate kit
80199
Oil pump kit
80290
Oil sump heater kit (220-240 V)
80237
Only use genuine GEA spare parts!
7.3 Recommended spare parts
7.1 Preparation
WARNING
Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.
Содержание Bock HG8 Series