19
96389-08.2019-DGbFEIRu
Rigid
fixed point
As short
as possible
4
|
Compressor assembly
4.7 Operating the shut-off valves
Before opening or closing the shut-off valve, release the valve spindle seal by approx.
1
/
4
of a turn
counter-clockwise.
After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Fig. 14
Fig. 15
Valve spindle seal
Release
Tighten
4.6 Laying suction and pressure lines
Fig. 13
A rule of thumb:
Always lay the first pipe section starting from the shut-off valve
downwards and
parallel to the drive shaft.
ATTENTION Improperly installed pipes can cause cracks and tears which can
result in a loss of refrigerant
INFO
Proper layout of the suction and pressure lines directly after the com-
pressor is integral to the smooth running and vibration behaviour of
the system.
a)
a) For EX-HG44e a intermediate flange (height 27 mm) is optional available,
Art-Nr. 81194.
With this intermediate flange it is possible to lay the pressure line directly from
the valve to the left or right.