background image

          

Installation Sheet No. 1337ZE R3.0 

 

 

Z630-3 Conventional Optical Smoke Detector 

 Page 

501-1337ZE-1 

 www.gesecurity.eu

 

 Copyright © 2007 GE Security B.V. All rights reserved 

12 November 2007 

Figure 1: Mounting the detector 

Detector Housing

Component

Cover Plate

Component
Cover Plate

Housing Assy

Screw

Housing Assy

Screw

Housing Assy

Screw

Housing Assy

Screw

2437-01

Top View

Bottom View

Indent -
Zone Labelling

 

Installation instructions 

Note:

  No wiring is required during detector installation. 

Refer to base datasheet for line wiring installation. All 
installation should be in accordance with the 

requirements of the authority having jurisdiction. 

Refer to Figure 1. The detector attaches to compatible 

bases with a plug-and-twist action as follows: 

1.  Align the detector with the base and turn it slowly 

until the location lugs and grooves mate, allowing 
the detector to slide completely into the base. 

2.  Rotate the detector clockwise until it locks. To 

remove the unit from the base, perform these steps 
in reverse order. 

Note:

 

To prevent unauthorized removal, a plastic breakout 
tab is provided in the detector housing. Once the 
breakout tab is removed the detector can only be 

released by use of a special tool. 

Functional test 

3.  Prior to initial testing remove the yellow plastic dust 

cover from the detector and notify the proper 

authorities that the fire alarm system is undergoing 
maintenance and will be temporarily out of service. 

Refer to local codes prior to testing. 

Perform a functional test using an aerosol detector 

tester. 

4.  An indent is provided on the detector exterior for 

application of Zone number labelling to allow easy 
zone identification. 

Warnings: 

This device detects smoke from slow burning 
to smouldering fires, and should only be used 

as part of a broad-based life safety system. 
For further information consult your local fire 

protection specialist. 

5.  For head out continuity, a diode base must be used 

and zone wiring must be terminated with a suitable 
end of line (EOL) component. The choice of EOL is 
dependant on the control panel used (refer to 

Control Panel datasheet). For Control panels 
without a head out facility, an active end of line unit 
may be used. 

 

Maintenance should be planned in 

accordance with the requirements of the 

authority having jurisdiction. 

 

 

Cleaning 

Refer to Figure 1. 

1.  Refer to local codes prior to cleaning. 
2.  Remove housing screws and the exterior. Remove 

the optic chamber by releasing the catch on the 
edge of the chamber and twisting the chamber out.  
Care should be taken not to damage the insect 
mesh window during this operation. 

3.  Clean the inside of the chamber using compressed 

air. 

4.  Clean the optics and insect mesh windows using 

alcohol and cotton buds. 

5.  Reassemble optic chamber and detector. 
6.  Check device is functioning correctly. 
7.  If the device is not functioning correctly, return to 

your supplier. 

 

Отзывы: