Installation Sheet No. 1337ZE R3.0
Z630-3 Conventional Optical Smoke Detector
2435-01
Brief description
The Conventional Optical Smoke Detector provides an
early response to a wide range of slow burning to
smouldering fires, and provides reliable sensing for
most conventional fire alarm applications. The detectors
aesthetic design and proven stability in air movements
associated with air conditioning systems, have made it
an ideal selection for modern building interiors.
Specifications
General information
Designation
Optical Smoke Detector
Specification
EN54 Part 7
Sensitivity 0.1
dB/m
Model number
Z630-3
Part number
1337
Compatibility
Compatible 24 V conventional
systems
Mounting
Plugs into surface or semi
recessed base
Area coverage
80 m², subject to local codes
Wiring 2-wire
zonal
Monitoring
Base
Open and short circuit by end of
line resistor
Diode base
Open and short circuit, and head
out continuity with suitable end
of line (EOL) component.
Indication
Alarm LED (red)
Detection principle
Photo electric light scatter
Environmental
Application Indoor
use
Environmental rating
IP32
Temperature range
-20 to +70ºC
Humidity range
20 to 95% RH (non condensing)
Primary supply
Operating voltage
12 to 30 VDC
Current (quiescent)
<60 µA @ 24 VDC
Current (alarm)
Maximum 50 mA (limited by panel)
Mechanical details
Material Moulded
ABS
Colour White
Dimensions (D x H)
106 x 52 mm – excluding base
Height (from ceiling
with base)
surface base – 60mm
recessed base – 38mm
Weight
100 g (excluding base)
Manufacturer traceability
A barcode label is affixed to each product (see example
below). This label reflects, amongst other things, the date of
manufacture of the product in the form YYDDD.
These numbers are interpreted as follows:
YY = year of manufacture
DDD = day of manufacture
For example the numbers 07134 would indicate that the
product was manufactured on the 134
th
day of the year 2007,
that is 14
th
May 2007.
Page
1
501-1337ZE-1
www.gesecurity.eu
•
Copyright © 2007 GE Security B.V. All rights reserved
12 November 2007