Chapter 9 Errors: Messages and removal
9-5
9.3
Parameterization errors
In order to determine what type of parameterization error has occurred, use the
corresponding control software to access the safe controller online and read the error.
9.4
PROFIsafe errors
In addition to the module errors specified, the following errors can occur:
–
PROFIsafe system errors: These messages can be found in Section "Diagnostic
messages for parameter errors" on page B-3.
–
PROFIBUS or PROFINET system errors: For information about these errors, please
refer to the documentation for the system used.
Table 9-5
Parameterization errors
Error cause
Error code
(hex)
LED
Remark
Effect
Remedy
Acknow-
ledgment
Incorrect
parameterization
See
Table 9-6
FS LED
(flashing)
Each output is
parameterized
individually
Module is in the
safe state
Check and correct
parameterization.
–
Table 9-6
Parameterization errors
Error code
Short description
Remedy
(hex)
(dec)
X23n
X230: OUT0_Ch1&2
X231: OUT1_Ch1&2
560
: OUT0_Ch1&2
561
: OUT1_Ch1&2
The parameterization of two related outputs
does not correspond to the two-channel
setting.
Correct value and resend
parameter data to the module.
X28n
X280: OUT0_Ch1
X281: OUT1_Ch1
X287: OUT0_Ch2
X281: OUT1_Ch2
640
: OUT0_Ch1
641
: OUT1_Ch1;
647
: OUT0_Ch2
648
: OUT1_Ch2
The parameterized switch-off delay time for
the output is outside the permissible value
range.
Correct value and resend
parameter data to the module.
X29n
X290: OUT0_Ch1&2
X291: OUT1_Ch1&2
656
: OUT0_Ch1&2
657
: OUT1_Ch1&2
For outputs parameterized for two-channel
operation, the same settings were not
assigned for the switch-off delay.
Correct setting and resend
parameter data to the module.
X2An
X2A0: OUT0_Ch1
X2A1: OUT1_Ch1
X2A7: OUT0_Ch2
X2A8: OUT1_Ch2
672
: OUT0_Ch1
673
: OUT1_Ch1;
679
: OUT0_Ch2
680
: OUT1_Ch2
Impermissible assignment of an alarm input.
Either more than one alarm input is assigned
to an output or the selected alarm input has
already been assigned to another output.
Dual assignment is only supported for
two-channel outputs.
Correct setting and resend
parameter data to the module.
X2F2
754
At least one output with parameterized
switch-off delay is still performing a switch-off
operation.
Wait until the switch-off
operation is complete and
resend parameter data to the
module.
Содержание VersaSafe VersaPoint IC220SDL840
Страница 2: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y ...
Страница 6: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 34: ...2 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 2 18 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 48: ...4 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 4 8 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 54: ...5 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 5 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 84: ...7 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 7 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 88: ...8 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 8 4 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 96: ...10 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 10 2 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 106: ...11 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 11 10 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 120: ...C T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y C 8 User manual IC220SDL840 May 2018 GFK 2734 ...