Chapter 6 Diagnostics
6-17
6
Profibus – Device-Specific Diagnostics (For NIU Model IC670PBI002)
Byte Meaning
Explanation
0-5
Profibus standard diagnostics
0 Station status
1
1
Station status 2
2 Station status 3
3 Profibus master address
4 00
H
manufacturer identification high
byte
06
H
manufacturer identification high
byte
5 F0
H
manufacturer identification low
byte
CC
H
manufacturer identification low
byte
6
09 H header byte
Number of device-specific diagnostic bytes
7
8
1
H
Diagnostics version
8
Device Number
Slot
9
Specifier
0 = No change
1
= Error present
2 = Error no longer present
1
0
Error type
0 = No error
1
= Profibus Parameter Error (SetPrm)
2 = Profibus Configuration Error (Chk_Cfg)
3 = Other configuration error
4 = Error within the I/O Station
5 = Module error
6 = Parameter error in the I/O Station
For information about error type, see “Determining
the Error Cause and Remedy” earlier in this
chapter.
11
Error number
0 to
1
2. Depends on error type.
For information about error number, see
“Determining the Error Cause and Remedy” earlier
in this chapter.
1
2
ID Code
0 to 255
1
3
Status Length Code
0 to 255
1
4
4
1
H Software
version
Содержание VersaPoint IC220PB001
Страница 4: ......
Страница 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Страница 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Страница 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Страница 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...