Process Data Input Words in the Event of an Error
In the event of an error, the command is mirrored in the input word IN[0] and displayed with the set
error bit. The input word IN[1] indicates the error cause.
The following diagnostic codes are valid for configuration or hardware errors in all data formats:
In addition to the indicator in the input words, for diagnostic codes 8040
hex
(module faulty) and
8020
hex
(I/O supply voltage faulty), a peripheral fault is reported to the higher-level control system.
The "IB IL" and "standardized display" formats offer additional diagnostic functions.
These are specified on page 16 and page 23.
Command
(hex)
Code
(hex)
PF
Meaning/Note
Remedy
8020
X
I/O supply voltage faulty.
–
Check the supply voltage of
the station head (e.g., U
BK
).
–
Check the potential jumper
connection.
After module
start
8040
X
Module faulty.
Replace module.
0x00
8004
There is no valid configuration for
the channel scanned.
Configure channel.
5x00
8004
The configuration just specified is
invalid.
Check and correct configuration.
1x00
8010
There is no valid configuration for
the channel scanned.
Configure channel.
4x00 and
6000
The parameters are mirrored. This
is usually caused by invalid para-
meters.
Check and correct parameters.
3C00
No diagnostic code.
PF
A peripheral fault is reported to the higher-level control system