10.1
Bit Operation Functions
The Bit Operation functions perform comparison, logical, and move operations on bit
strings. The Bit Operation functions are:
•
Logical AND
•
Logical OR
•
Exclusive OR
•
Logical Invert (NOT)
•
Shift Right/Shift Left
•
Rotate Right/Rotate Left
•
Bit Test
•
Bit Set, Bit Clear
•
Masked Compare
•
Bit Position
•
Bit Sequencer
10.1.1
Data Lengths for the Bit Operation Functions
The Logical AND, OR, XOR, and NOT (Invert) functions operate on a single word of
data. The other Bit Operation functions may operate on up to 256 words.
All Bit Operation functions require Word-type data. However, they operate on data as a
continuous string of bits, with bit 1 of the first word being the Least Significant Bit
(LSB). The last bit of the last word is the Most Significant Bit (MSB). For example, if
you specified three words of data beginning at reference %R0100, it would be operated
on as 48 contiguous bits.
%R0100
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
←
bit 1
(LSB)
%R0101
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
%R0102
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
↑
(MSB)
Overlapping input and output reference address ranges in multi-word functions is not
recommended, it can produce unexpected results.
10.1.2
Bit Operation Functions Logical AND, Logical
OR
Each scan that power is received, a Logical AND or Logical OR function examines each
bit in bit string I1 and the corresponding bit in bit string I2, beginning at the least
significant bit in each. A string length of 256 words can be selected.
10.1.2.1
Logical AND
If both bits examined by the Logical AND function are 1, a 1 is placed in the
corresponding location in output string Q. If either or both bits are 0, a 0 is placed in
string Q in that location. The Logical AND function can be used to build masks or
screens, where only certain bits are passed through (bits opposite a 1 in the mask), and all
other bits are set to 0. The Logical AND function can also be used to clear an area of
word memory by ANDing the bits with another bit string known to contain all 0s. The I1
and I2 bit strings specified may overlap.
124
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...