GE Multilin
C70 Capacitor Bank Protection and Control System
B-19
APPENDIX B
B.4 MEMORY MAPPING
B
409B
DNP Channel 2 Port
0 to 4
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409D
Reserved
0 to 1
---
1
F001
0
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
1 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
1 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
1 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
1 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP unsolicited responses maximum retries
1 to 255
---
1
F001
10
40AC
DNP unsolicited responses destination address
0 to 65519
---
1
F001
1
40AD
Ethernet operation mode
0 to 1
---
1
F192
0 (Half-Duplex)
40AE
DNP current scale factor
0 to 8
---
1
F194
2 (1)
40AF
DNP voltage scale factor
0 to 8
---
1
F194
2 (1)
40B0
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B1
DNP energy scale factor
0 to 8
---
1
F194
2 (1)
40B2
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B3
DNP other scale factor
0 to 8
---
1
F194
2 (1)
40B4
DNP current default deadband
0 to 65535
---
1
F001
30000
40B6
DNP voltage default deadband
0 to 65535
---
1
F001
30000
40B8
DNP power default deadband
0 to 65535
---
1
F001
30000
40BA
DNP energy default deadband
0 to 65535
---
1
F001
30000
40BE
DNP other default deadband
0 to 65535
---
1
F001
30000
40C0
DNP IIN time synchronization bit period
1 to 10080
min
1
F001
1440
40C1
DNP message fragment size
30 to 2048
---
1
F001
240
40C2
DNP client address 3
0 to 4294967295
---
1
F003
0
40C4
DNP client address 4
0 to 4294967295
---
1
F003
0
40C6
DNP client address 5
0 to 4294967295
---
1
F003
0
40C8
DNP number of paired binary output control points
0 to 32
---
1
F001
0
40C9
DNP TCP connection timeout
10 to 65535
---
1
F001
120
40CA
Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP port number for the IEC 60870-5-104 protocol
1 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 protocol function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 protocol common address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 protocol cyclic data transmit period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 current default threshold
0 to 65535
---
1
F001
30000
40E6
IEC 60870-5-104 voltage default threshold
0 to 65535
---
1
F001
30000
40E8
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EA
IEC 60870-5-104 energy default threshold
0 to 65535
---
1
F001
30000
40EC
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EE
IEC 60870-5-104 other default threshold
0 to 65535
---
1
F001
30000
40F0
IEC 60870-5-104 client address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 redundancy port
0 to 1
---
1
F126
0 (No)
4005
Reserved (59 items)
0 to 1
---
1
F001
0
4140
DNP object 1 default variation
1 to 2
---
1
F001
2
4141
DNP object 2 default variation
1 to 3
---
1
F001
2
4142
DNP object 20 default variation
0 to 3
---
1
F523
0 (1)
4143
DNP object 21 default variation
0 to 3
---
1
F524
0 (1)
4144
DNP object 22 default variation
0 to 3
---
1
F523
0 (1)
4145
DNP object 23 default variation
0 to 3
---
1
F523
0 (1)
4146
DNP object 30 default variation
1 to 5
---
1
F001
1
Table B–9: MODBUS MEMORY MAP (Sheet 12 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...