GE Multilin
T60 Transformer Protection System
5-331
5 SETTINGS
5.9 TRANSDUCER INPUTS AND OUTPUTS
5
5.9.3 RRTD INPUTS
a) MAIN MENU
PATH: SETTINGS
TRANSDUCER I/O
RRTD INPUTS
Menus are available to configure each of the remote RTDs.
Table 5–38: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
RESISTANCE (IN OHMS)
°C
°F
100
Ω
PT
(DIN 43760)
120
Ω
NI
100
Ω
NI
10
Ω
CU
–50
–58
80.31
86.17
71.81
7.10
–40
–40
84.27
92.76
77.30
7.49
–30
–22
88.22
99.41
82.84
7.88
–20
–4
92.16
106.15
88.45
8.26
–10
14
96.09
113.00
94.17
8.65
0
32
100.00
120.00
100.00
9.04
10
50
103.90
127.17
105.97
9.42
20
68
107.79
134.52
112.10
9.81
30
86
111.67
142.06
118.38
10.19
40
104
115.54
149.79
124.82
10.58
50
122
119.39
157.74
131.45
10.97
60
140
123.24
165.90
138.25
11.35
70
158
127.07
174.25
145.20
11.74
80
176
130.89
182.84
152.37
12.12
90
194
134.70
191.64
159.70
12.51
100
212
138.50
200.64
167.20
12.90
110
230
142.29
209.85
174.87
13.28
120
248
146.06
219.29
182.75
13.67
130
266
149.82
228.96
190.80
14.06
140
284
153.58
238.85
199.04
14.44
150
302
157.32
248.95
207.45
14.83
160
320
161.04
259.30
216.08
15.22
170
338
164.76
269.91
224.92
15.61
180
356
168.47
280.77
233.97
16.00
190
374
172.46
291.96
243.30
16.39
200
392
175.84
303.46
252.88
16.78
210
410
179.51
315.31
262.76
17.17
220
428
183.17
327.54
272.94
17.56
230
446
186.82
340.14
283.45
17.95
240
464
190.45
353.14
294.28
18.34
250
482
194.08
366.53
305.44
18.73
RRTD INPUTS
RRTD 1
MESSAGE
RRTD 2
↓
MESSAGE
RRTD 12
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...