CHAPTER 5: SETTINGS
SYSTEM SETUP
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
5-159
5
The thermal inputs settings are used for computation of hottest-spot winding temperature, aging factor, and accumulated
loss of life.
WINDING CURRENTS
— Enter a source that represents the true winding load currents.
In cases where two or more sets of CTs are associated to the winding and where thermal elements are to be set (for
example, in a breaker-and-a-half scheme), use a spare source for current summation from these CTs to obtain the total
true winding current. Otherwise, select the only source representing the other winding current.
AMBIENT TEMPERATURE
— Select an RTD, DCmA, or remote RTD input if the ambient temperature is to be measured directly.
Otherwise, select “Monthly Average” and enter an average temperature for each month of the year if a directly measured
device output is not available (see the monthly settings that follow).
TOP OIL TEMPERATURE
— Select RTD, DCmA, or remote RTD input for direct measurement of top-oil temperature. If an RTD or
DCmA input is not available, select “Computed.”
The following menu displays when
AMBIENT TEMPERATURE
is “Monthly Average.”
SETTINGS
SYSTEM SETUP
TRANSFORMER
THERMAL INPUTS
AMBIENT TEMPERATURE
5.5.5 Breakers
SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(6)
AMBIENT TEMPERATURE:
Monthly Average
JANUARY AVERAGE:
–20°C
Range: –60 to 60°C in steps of 1
FEBRUARY AVERAGE:
–30°C
Range: –60 to 60°C in steps of 1
MARCH AVERAGE:
–10°C
Range: –60 to 60°C in steps of 1
DECEMBER AVERAGE:
–10°C
Range: –60 to 60°C in steps of 1
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
BREAKER 1 TAGGING:
Disabled
Range: Disabled, Enabled
BREAKER 1
SUBSTITUTN: Disabled
Range: Disabled, Enabled
BREAKER 1 BYPASS:
Disabled
Range: Disabled, Enabled
BREAKER 1 NAME:
Bkr 1
Range: up to six alphanumeric characters
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BREAKER 1 OPEN:
Off
Range: FlexLogic operand
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic operand
BREAKER 1 CLOSE:
Off
Range: FlexLogic operand
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic operand
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...