background image

3

Mounting inside Concord Commercial enclosure

Note:  

This module is UL listed as a subassembly and must be 
mounted in the same enclosure as the Concord 4 in UL 
systems.

1.

Unplug the panel AC power transformer and disconnect the 

backup battery.

2.

Remove the necessary knockouts for wire access (Figure 7).

3.

Place the cabinet at the desired location and mark the 

cabinet mounting holes and knockouts (Figure 7).

Figure 7.

Commercial enclosure power supply mounting holes and knockouts

4.

Drill holes and insert the appropriate anchors where studs 
are not present.

5.

Run wires from all devices to be powered, to the power 

supply.

6.

Run a 4-conductor, 22-gauge or larger stranded wire from 
the power supply to the panel.

7.

Run a 2-conductor, 18-gauge stranded wire from the power 
supply to the AC transformer location.

8.

Feed all wires through the knockouts and secure the cabinet 

to the wall with the included screws.

9.

Secure the power supply to the cabinet using either the right 
side or left side power supply mounting holes, with the six 
self-tapping screws included with the power supply (Figure 

8).

Figure 8.

Power supply mounted in commercial enclosure

Wiring

Connect the power supply to the panel terminals and devices as 
shown in Figure 9.

Figure 9.

Power supply wiring connections to panel and devices

Power Up

Use the following procedure for powering up the power supply 
and panel to verify bus communication.
1.

Verify that all wiring at the panel and devices are correct.

2.

Connect the power supply backup battery to the battery 
terminals on the power supply board (Figure 10).

Figure 10. Power supply AC and DC power connections

3.

Wire the power supply AC transformer to the power supply 
board, then plug in the transformer (Figure 10).

 

The green LED should turn on to indicate power is present.

 

The red LED should be off for the moment.

Note:  

If the green LED is not on, unplug the power supply AC 
power transformer, disconnect the backup battery, and 
proceed to Table 2 in “Troubleshooting”.

4.

Connect the panel backup battery and plug in the panel AC 

power transformer.

 

The panel should automatically scan for new bus devices 
and the red LED on the power supply board should flicker 

to indicate bus communication with the panel.

5.

If using the optional zone input, learn the zone into panel 
memory (see panel 

installation instructions

).

Cabinet

Mounting

Holes (4)

Knockouts (4)

Power Supply

Mounting

Holes

Right Side Mounting

Left Side Mounting

2 4 V A C 2 4 V A C + 1 2 V

B U S A

B U S B

G N D

+ 1 2 V

O U T

Z O N E

G N D

G N D

3

4

5

6

+ 1 2 V

A

B

G N D

B U S

To power

N/O circuit with2k Ohm 

inputs on
devices

Resistor (49-45

4)

N/C circuit with 2k Ohm 

Resistor (49-454)

To bus

devices

2 4 V A C 2 4 V A C + 1 2 V

B U S A

B U S B

G N D

+ 1 2 V

O U T

Z O N E

G N D

G N D

+

_

+

_

RED

BLACK

Содержание SuperBus 2000

Страница 1: ...l is 4 000 feet When mounting the power supply in a separate enclosure the power supply mounting location should be determined by the wire runs needed to provide power to devices with minimal loss on the 12V OUT wire Table 1 shows the maximum wire runs between the power supply 12V OUT terminal and the devices it will power For UL installations the 12V OUT is not fully supervised for open circuits ...

Страница 2: ...cord 4 in UL systems 1 Unplug the panel AC power transformer and disconnect the backup battery 2 Place the cabinet at the desired location and mark the cabinet mounting holes and knockouts Figure 5 Figure 5 Residential enclosure mounting holes and knockouts 3 Drill holes and insert the appropriate anchors where studs are not present 4 Run wires from all devices to be powered to the power supply 5 ...

Страница 3: ...to panel and devices Power Up Use the following procedure for powering up the power supply and panel to verify bus communication 1 Verify that all wiring at the panel and devices are correct 2 Connect the power supply backup battery to the battery terminals on the power supply board Figure 10 Figure 10 Power supply AC and DC power connections 3 Wire the power supply AC transformer to the power sup...

Страница 4: ...nal 2 Verify that devices connected to power supply 12V OUT terminal are not drawing more than 2 amps System touchpads display AUX POWER BATT trouble 1 Check that power supply battery is connected 2 Power supply battery needs charging Battery may need at least 4 hours to fully charge System touchpads display AUX AC POWER trouble 1 Check that power supply transformer is plugged into outlet 2 Check ...

Отзывы: