SPS J200703 L005
–
Quick Start Guide
5
Document 850052515 r02 2019 April
GE
Critical Power
SPS –48V Slimline Power Shelf
Models: J2007003L005 - alpha suffixes per Slimline Power System Brochure
Quick Start Guide
Document xxxxxxxxxx R01 2017 August
5
Information Alarm Connections
See the Slimline Power System Brochure for details.
Alarm connections are on the rear of the shelf – J1 is the Alarm Outputs and J2 is Alarm Inputs
Change alarm descriptions via LAN port (Web pages)
Connector
J1 – Controller Variants
J2 – All Controllers
Pin Controller
Color
015R_D – 5 Relays
016R_DS-6
3C3R – 3 /Relays,
3 Inputs
9C0R-USB – 9 Inputs,
(No relays)
Color
All
1
BK
Output: R3 = Rtn
Input: PBT/TR
Input: Door Open
Y
Input: SPD Fail
2
BR
Output: R2 = Rtn
Input: Hi Ext. Temp
Input: Surge Protect Fail
S
--
3
R
Output: R1 = Rtn.
Output: R1 = Rtn.
Input: Door 2 Open
O
Input: AUX MAJ
4
O
Output: PMN Rtn
Output: PMN Rtn
Input: Ext DC Fail Major
V
Input: Air Con. Fail
5
Y
Output: PMJ Rtn
Output: PMJ Rtn
Input: Ext DC Fail Minor
W
Input: Door Open
6
G
Output R3 = ACF
Input: RTNS
Input: Returns
BL
-48V
7
BL
Output R2 = RFA
Input: Cust. Alm 1
Input: Retrieve Generator
BR
-48V
8
V
Output: R1 = BD
Output: R1 = BD
Input: Battery Fail
BK
-48V
9
S
Output: PMN
Output: PMN
Input: Air Conditioner Fail
Output: R4 = FAJ
1
10
W
Output: PMJ
Output: PMJ
Input: External Fan Fail
Output: R4 = Rtn
1,2
1.
Only with 6 relay controller (..6R..).
2.
Returns for R1 and R4 are bridged. Other returns are isolated.
Specifications and Application
•
Specifications and ordering information are in the Slimline Power System Brochure available at
www.gecriticalpower.com
•
External Surge Protective Devices (SPDs) - are required on all AC inputs.
Equipment Safety is Approved in IEC 60664-1 Installation Category II environments.
•
Equipment and subassembly ports:
1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
•
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane
(Mesh-Bonding Network or Common Bonding Network).
•
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
•
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at
www.gecriticalpower.com
.
Document Title:
850035894 Galaxy Pulsar Edge Quick Start Guide
CC848836981 Pulsar Edge Controller Family Product Manual
Temperature:
North America
–
50°C Max. with no derating. 2% / °C derating above 50°C to 75°C.
CE
–
50°C Max.